Forsyth · Code of Ordinances
Chapter 23 - UTILITIES / Article VI - ELECTRIC
Sec. 23-148. Emergency electric service disconnects.
About this text
- As posted on the city's website, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) All commercial electric services up to and including 600 amps shall have a manual disconnect installed in a readily accessible outdoor location. Adequate markings labeling the disconnect as “Emergency” disconnect shall be installed on or near disconnect.
(b) All commercial electric services above 600 amps shall have an emergency disconnect installed in a readily accessible outdoor location. A shunt trip main breaker wired to emergency disconnect switch may be used in leu of a manual disconnect on commercial electric services of this size. Adequate markings labeling the disconnect as “Emergency” disconnect shall be installed on or near disconnect.