Jasper · Code of Ordinances

Part II - CODE OF ORDINANCES / Chapter 30 - FIRE PREVENTION AND PROTECTION / Article III - FIRE CODE

903.2.1.3. Group A-3.

About this text

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy

where one of the following conditions exists:

1. The fire area exceeds 12,000 square feet (1115 m2 ).

2. The fire area has an occupant load of 300 or more.

3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.

Read this code where it is posted (Municode) The source is the city's code as its publisher or its own website posts it. Check it there for later changes.

Version local-code:jasper/code/903.2.1.3@2026-11-11-589324f288