Part II - CODE OF ORDINANCES / Chapter 30 - FIRE PREVENTION AND PROTECTION / Article III - FIRE CODE
903.2.1.1. Group A-1
About this text
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancy and throughout all stories from the Group A-1 occupancy to and including the levels of exit discharge serving the occupancy
where one of the following conditions exists:
1. The fire area exceeds 4,999 square feet (464.4222 m2 ).
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.
4. The fire area contains a multiple-theater complex.