An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists: 1. A Group S-1 fire area exceeds 4,999 square feet (464.4222 m2 ). 2. A Group S-1 fire area is located more than three stories above grade plane. 3. The combination area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929.030 m2 ). 4. A Group S-1 occupancy used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m2 ). 5. A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m2 ). (7) Modify the adopted Georgia State Minimum Fire Code NFPA 101 to add the following: Any reference to a square footage requirement for the installation of an automatic sprinkler system in chapter 12 through 43 shall be amended to require automatic sprinklers installed in structures over 4,999 square feet. Existing exemptions referenced in the adopted International Fire Code shall be applicable to this modification. (8) Modify the adopted Georgia State Minimum Standard Fire Code 230.7(A)(l) of the National Electrical code from: 230.7(A)(l) Readily Accessible Location. The service disconnecting means shall be installed at a readily accessible location either outside of a building or structure or inside nearest the point of entrance of the service conductors. Replace the previous text of 230.70(A)(l) with: 230.70(A)(l) Readily Accessible Location. The service disconnecting means shall be installed at a readily accessible location outside of a building or structure nearest the point of entrance of the service conductors.