73-7.4.3. Cryptocurrency Mining Operations.

About this text

  • As published by Municode, current through 2026-02-09
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Server Farms, and/or Data Centers.

A facility or portion of a facility housing networked computer systems and telecommunications equipment used for remote storage, processing, and distribution of data, including facilities where commercial cryptocurrency transactions are verified and added to the public ledger, through the use of server farms employing data processing equipment. Such facilities shall comply with the following:

A. Fire Safety Requirements.

1. Fire Suppression. An active clean agent fire protection system shall be provided and maintained in good working order within any structure. High sensitivity smoke detectors shall be installed and operational in order to activate this clean agent fire suppression system.

2. There shall be an emergency electricity termination switch installed outside of any containment structure.

3. Containment Space. The equipment used shall be housed in an individually metered, electrically grounded and metal-encased structure with a fire rating designed to resist an internal electrical fire for at least 30 minutes. The containment space shall contain baffles that will automatically close in the event of fire independent of a possible electric system failure.

4. All building requirements required by this section, including but not limited to heat transfer apparatuses, fire detection/suppression systems, or containment structures shall be designed by a Georgia licensed engineer and in accordance with all applicable codes and standards.

B. Heat Safety Requirements.

1. The ambient temperature inside of a containment space shall not exceed 120 degrees Fahrenheit at any time. No person shall be permitted to regularly inspect and work within the containment area if the ambient temperature within the containment area exceeds 90 degrees Fahrenheit.

2. No more than 20% of the heat dissipated by the mining activity shall be released directly to the outside when the average daily temperature is less than 40 degrees Fahrenheit.

C. Nuisance Abatement.

1. No adverse or detrimental effects shall impact adjoining properties, owners, or residents that diminish the quality of life or increase the costs of serving their business or maintaining their homes.

2. A noise level exceeding ninety decibels (90 dB) from a distance of twenty-five feet from the exterior of the containment structure is prohibited.