--- title: Adairsville Zoning Ordinance, Sec. 47-178. Data centers and related technology uses collection: local-codes id: local-code:adairsville/zoning/47-178 cite_as: Adairsville, Ga., Zoning Ordinance § 47-178 canonical_url: https://georgiacommons.org/code/local/adairsville/zoning/47-178 md_url: https://georgiacommons.org/code/local/adairsville/zoning/47-178.md text_url: https://georgiacommons.org/code/local/adairsville/zoning/47-178/text source_url: https://library.municode.com/ga/adairsville date: 2026-08-20 status: active jurisdiction: city:adairsville jurisdiction_name: Adairsville place_fips: "1300436" corpus_version: local-codes-adairsville-be642d4dbcb0 publisher: Georgia Commons, an independent project of Georgia Civic Data. Not the State of Georgia. Not legal advice. up: https://georgiacommons.org/code/local/adairsville/zoning/~part-ii/~chapter-47/~article-vii.md previous: https://georgiacommons.org/code/local/adairsville/zoning/47-177.md next: https://georgiacommons.org/code/local/adairsville/zoning/47-179-to-47-205.md index: https://georgiacommons.org/code/local/adairsville.md branch: zoning edition: As published by Municode, current through 2026-08-20 edition_date_kind: current_through source_publisher: Municode version_id: local-code:adairsville/zoning/47-178@2026-08-20-896b4f72e6 --- # Adairsville Zoning Ordinance, Sec. 47-178. Data centers and related technology uses > As published by Municode, current through 2026-08-20 > The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included. Part of: Part II - CODE OF ORDINANCES / Chapter 47 - ZONING / Article VII - DETAILED REGULATIONS FOR SPECIFIC USES (a) Purpose. The purpose of this section is to regulate data centers and related technology uses, as provided herein, and which supports and encourages the siting of new technologies, computer systems, data infrastructure and data hosting. (b) Use regulations. Data centers and related technology uses, where permitted under the table of permitted uses, shall be subject to the requirements of this section. (1) Uses permitted as data centers and related technology uses include: Computer systems and facilities design, programming operation and management. Data processing, storage, hosting and related services. Information product research and development. Internet website design and hosting. Public utility facilities. Software design and development. Solar, renewable and alternative energy facilities. Technology consulting and management. Telecommunications infrastructure and connectivity facilities. (2) Uses not permitted as data centers and related technology uses are: The commercial process by which cryptocurrency transactions are verified and added to the public ledger, known as the block chain, and also the means through which new units of cryptocurrencies are released, otherwise known as cryptocurrency mining, which is not permitted as a data center. (3) Accessory uses. Structures and land may be used for uses customarily incidental to any permitted use. (c) Development standards. (1) Data center development. A data center development shall mean and refer to the entire contiguous tract of land presented for development as a data center. (2) Height regulations. Buildings shall not exceed a height of 75 feet, measured from structure pad level. Height limitations shall not apply to accessory structures such as water towers, conveyer belts, HVAC equipment, generators and other incidental and uninhabited parts of the structure. (3) Size, buffers and setbacks. a. Minimum acreage: 450 acre parcel(s). b. Buffers and setbacks. All buffers and setbacks shall conform to the development agreement or the requirements of the zoning district, whichever is most restrictive. (4) Minimum buffer requirements. In addition to required setbacks, a minimum 200-foot wide buffer, which can include required setback, shall be required along all property lines which abut a residential district or O/I district, 50 feet when adjacent to the C-1 or C-2 district use in order to provide a visual screen. (5) Air conditioning units and HVAC systems. Air conditioning units and HVAC systems shall be thoroughly screened from view from the public right-of-way and from adjacent properties by using walls, fencing, roof elements, or landscaping. This requirement shall not apply where the equipment is more than 100 feet from adjacent property lines. (6) Front building facade. The front building facade of all principal buildings shall be oriented toward street fronts or adjacent arterial street fronts. This requirement shall not apply if the front of the building is greater than 500 feet from the public right-ofway or not visible from the public right-of-way. (7) Security fencing and structures. Security fencing and walls shall not be located within the required buffer unless it complies with the general regulations pertaining to fencing. Fences and walls outside the required setback and buffer provided above shall not be subject to height limitations. Guard houses and secured entry features shall be permitted at public road entrances. (8) Exception for internal lots. Required setbacks and buffers shall only apply to external property boundaries with other properties not part of the data center campus. Minimum lot frontages, width and acreage shall not apply to subdivided lots within the data center campus, so long as the entirety of the contiguous data center campus complies with the requirements of this section, and so long as the subdivided lot has adequate frontage on public or private roads to allow service. (9) Private roads. Private roads are permitted within data center campuses. (10) Dark sky lighting. Exterior illumination shall be shielded, downcast and of a luminosity designed to maintain the existing night sky darkness and to prevent light trespass onto adjacent properties. In order to obtain that objective, the following criteria shall be met: a. All fixtures shall be full cut-off type fixtures. b. Light poles shall be no taller than 25 feet in height. c. All light poles must be setback a minimum of ten feet from any exterior property line. d. Maximum foot-candles at the property line shall be 0.5. The community development director may require a photometric lighting plan which shows conformity with these requirements as part of any building permit application. (11) Sound control. In order to ensure that data centers and related technology uses do not contribute to noise pollution within the city, all data centers will be subject to the following standards: a. Data center operations shall not produce continuous sound that exceeds an average of 65 decibels over any 30-minute period from 8:00 a.m. to 6:00 p.m., measured at any adjacent property boundary between the data center site and a residential property. Nor shall data center operations produce continuous sound that exceeds an average of 55 decibels over any 30-minute period from 6:00 p.m. to 8:00 a.m., measured at any adjacent property boundary between the site and residential property. Violations of these sound levels may be prosecuted in the same manner as other zoning ordinance violations. b. After issuance of the certificate of occupancy for each data center building, the city may obtain sound studies or require the data center operator to provide a sound study to verify that the operation is in compliance with the requirements of subsection a. above. If a data center is found to be in violation of the requirements of subsection a. above, the city may issue a notice of violation, which may direct that the data center take appropriate steps to operate within the requirements of subsection a. above. The city manager may require the data center operator to propose a solution, and a time period for implementation. If the city manager approves such solution, and the data center fails to successfully implement that solution within the time approved, the violator shall be subject to a fine up to $1,000.00 for each day that the violation exists until full compliance is obtained. c. The data center operator shall continue to bear the costs of any sound test or study required to monitor violations in subsection b. above. (12) Data centers and related technology uses compliant with the requirements of this section are not subject to the requirement for special use permit review pursuant to section 47-393(c). (13) Developers of data centers desiring city utilities must request and receive from the city prior to any permits being issued or beginning construction a utility availability letter in compliance with section 45-2. Users of greater than 50,000 gpd of water or sewer must have their utility service approved by the mayor and council. In considering the proposed utility service, the mayor and council may consider the needs of the project, the available capacity of the city, and the anticipated future needs of the city and its customers. (14) Prior to the issuance of land disturbance permits, certificates of occupancy or other development approval the data center developer shall enter into a development agreement reasonably acceptable to the city whereby the developer will be financially responsible for any system upgrades required in providing for the installation of required project improvements and addressing the provision of public utilities to serve the project. The development agreement shall also provide that the developer will be responsible for all costs incurred by the city in investigating its ability to provide services to the project. If the city is unable to reasonably provide the required utilities to serve the project, then the city may decline to enter into a development agreement with the developer and therefore no land disturbance permits, certificates of occupancy or other development approval will be granted. ## History (Ord. No. 2025-0005, § 1, 7-17-2025)