506.1 General. The areas limited by Table 503 shall be permitted to be increased due to frontage (If ) and automatic sprinkler system protection (Is ) in accordance with the following: where: Aa = Allowable area per floor (square feet). At = Tabular area per floor in accordance with Table 503 (square feet). If = Area increase due to frontage (percent) as calculated in accordance with Section 506.2. Is = Area increase due to sprinkler protection (percent) as calculated in accordance with Section 506.3. 506.1.1 Basements. A single basement need not be included in the total allowable area provided such basement does not exceed the area permitted for a one-story building. 506.2 Frontage increase. Every building shall adjoin or have access to a public way to receive an area increase for frontage. Where a building has more than 25 percent of its perimeter on a public way or open space having a minimum width of 20 feet (6096 mm), the frontage increase shall be determined in accordance with the following: where: If = Area increase due to frontage (percent). F = Building perimeter which fronts on a public way or open space having 20 feet (6096 mm) open minimum width. P = Perimeter of entire building. W = Minimum width of public way or open space. 506.2.1 Width limits. W must be at least 20 feet (6096 mm) and the quantity W divided by 30 shall not exceed 1.0 except that for buildings which are permitted to be unlimited in area by Section 503.1.2, Section 507 or Section 508, the quantity W divided by 30 shall not exceed 2.0. Equation 5-1 Equation 5-2 506.2.2 Open space limits. Such open space shall be either on the same lot or dedicated for public use and shall be accessed from a street or approved fire lane. 506.3 Automatic sprinkler system increase. Where a building is protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, the area limitation in Table 503 is permitted to be increased by 200 percent (Is = 200 percent) for multi-story buildings and 300 percent (Is = 300 percent) for single-story buildings. Exception: Group H-1, H-2 or H-3.