A. Introduction. 1) |Across-connection can be generally defined as a physical connection between two otherwise separate piping systems or vessels, one of which contains potable water and the other does not. There are two main approaches to provide against actual or potential cross-connections, the "fixture outlet" approach and the "containment" approach. 2) With the "fixture outlet" approach, cross-connection control protective devices are placed at internal high hazard locations within the customer's internal water system as well as at all locations where cross-connections exist at the "last free-flowing outlet." This approach entails extensive crossconnection survey work on behalf of the water purveyor as well as constant policing of the plumbing within each customer's premises. In a large water supply system, fixture outlet protection is virtually impossible to achieve and police due to the quantity of systems involved, the complexity of the plumbing systems inherent in many industrial sites, and the fact that plumbing changes are made within industrial and commercial establishments that do not require approval or permitting. 3) The "containment" approach isolates the customer from the water main at all service connections, utilizing a minimum number of backflow devices throughout the system. Although this approach does not protect the customer within the building, it does effectively remove the possibility of contamination to the public water supply. 4) Due to the number of commercial customers and the difficulties associated with "fixture outlet" protection, the "containment" approach will be employed by the City of Canton for protection of the public water supply. B. Purpose. The purpose of the City of Canton Cross-Connection Control Program includes the following: 1) To protect the public water supply served by the City of Canton Water System from the entry of contaminants or pollutants into the system through the control of cross-connections. Control of contaminants or pollutants which could backflow or back-siphon into the public water system shall be accomplished by isolation and containment at the service connection. 2) To promote and encourage the elimination or control of existing cross-connections, actual or potential, between the customer's in-plant potable water system and nonpotable water systems, plumbing fixtures and industrial piping systems. 3) To provide for the maintenance of a continuing program of cross-connection control which will effectively prevent the contamination or pollution of all potable water systems by cross-connection. C. Authority. The Georgia Rules for Safe Drinking Water (391-3-5-13) state that a water supplier has the responsibility to prevent water from unapproved sources or any contaminants from entering the public water system. In partial fulfillment of this responsibility, the rules require that the water supplier develop a written program for the elimination and prevention of all cross-connections when requested by the Georgia Environmental Protection Division (EDP). D. Applicability. The provisions of backflow prevention by isolation and containment are applicable to any customer or system supplied by the City of Canton's water distribution system including irrigation sprinklers, fire protection systems, residential systems, and other service connections. E. Responsibilities. 1) The Council of the City of Canton is responsible for establishing regulations regarding the control of cross-connections to the public distribution system. 2) The city engineer is responsible for the enforcement of these regulations in an effort to protect the public water supply system through the prevention of backflow or back siphonage of contaminants or pollutants. This responsibility begins with the production of water and extends throughout the distribution system to the service connection, applying to new construction as well as to existing customers and situations. 3) The City of Canton Building Department is responsible for enforcing the city's adopted plumbing code regulations in an effort to prevent backflows on the customer's premises from entering the customer's own potable water system. This responsibility extends to both new and existing customers. 4) The water customer is responsible for complying with the city regulations including maintenance, testing, and reporting on certain devices. a. Customers are required to allow on-site inspections to verify compliance with the city's crossconnection control program. b. The customers have a dual responsibility for protecting the water in their own system from degradation due to conditions originating on their premises and for protecting the quality of water in the public distribution system. c. The customer is liable for any health hazard due to backflow from unprotected cross-connections on their premises. d. The customer is responsible for the costs of procurement, installation, testing, and maintenance of al backflow prevention devises on their premises and serving their premises. F. Reference material. The manuals listed below provide information relating to cross-connection control and backflow prevention. 1) Cross-Connection Control Manual, U.S. EPA Office of Water, June 1989, EPA 570/9-89-007. 2) Cross-Connection Control Manual, Ninth Edition. The EPA Cross Connection Control Manual defines, describes, and illustrates typical cross-Connections and suggest simple methods and devices to eliminate them. 3) Recommended Practice for Backflow Prevention and Cross Connection Control, AWWA Manual M14, 2nd edition, 1990. The AWWA manual sets forth criteria for the selection and installation of backflow prevention devices and outlines procedures and techniques for maintenance and inspection of these devices.