A. Hazard assessment. 1) Two degrees of hazard are considered, as determined by whether the impurities potentially involved are contaminants or pollutants. The two degrees of hazard, health and nonhealth, are defined below based on definitions given in the AWWA Manual M14 2nd edition: a. Health (contaminants).A cross-connection or potential cross-connection involving any substance that could, if introduced into the potable water supply, cause death, illness, spread disease, or have a high probability of causing such effects. b. Nonhealth (pollutants).A cross-connection or potential cross-connection involving any substance that generally would not be a health hazard, but would constitute a nuisance, or be aesthetically objectionable, if introduced into the domestic water supply. 2) Chapter 4 in the AWWA Manual M14 provides guidance for the assessment of hazard and selection of backflow protection assemblies for premises isolation. Information from the chapter is summarized in table 110-7. Chapter 5 of the AWWA Manual M14 and chapter 2 of the EPA Cross-Connection Control Manual provide additional examples and illustrations of customer types and typical cross-connections that pose hazards to the public water supply system. Table 110-7: Guidance for the Assessment of Hazard and Selection of Assemblies for Premises Isolation Description of Premises Assessment of Hazard Recommended Backflow Prevention Device at Service Connection Hospitals, mortuaries, clinics, laboratories Health RPZ Plants using radioactive material Health RPZ Petroleum processing or storage facilities Health RPZ Premises where inspection is restricted Health RPZ Sewage treatment plant Health RPZ Sewage lift stations Health RPZ Commercial laundry Health RPZ Car washing facilities Health RPZ Plating or chemical plants Health RPZ Docks and dockside facilities, pleasure-boat marinas Health RPZ Food and beverage processing plants Health RPZ Reclaimed water systems Health RPZ Auxiliary water supplies Health RPZ Tall buildings (protection against excessive head) Nonhealth DCVA Steam plants Nonhealth RPZ B. New customers. 1) The city building department shall review all plans for new construction and shall advise developers of regulations in advance and determine that appropriate protection measures and devices are proposed. 2) New construction will be inspected for City of Canton plumbing code compliance by inspectors in the city building department to determine that individual cross-connections are isolated from the public water supply. 3) The city will inspect all new service connections for cross-connection control compliance and determine the degree of hazard to the public water supply. Based on the hazard assessment, the city will require the customer to install an appropriately selected backflow prevention device. 4) Devices required by either the city building department or the cross-connection control program will be installed at the developer, builder, or owner's expense. 5) The city will refuse service in cases of noncompliance. C. Fire protection systems. 1) If the service connection to a premise is intended to be used for fire protection it shall be classified and/or defined as follows in table 110-8: Table 110-8 Fire Protection Systems — 1 Service Connection Definition Dedicated service connection One that is designated to supply potable water for fire protection service only Combination service connection One that is designed to supply potable water for both domestic use and fire protection service 2) The terminology and definitions for types of fire protection systems presented in table 110-9 shall also be applicable. 3) Sprinkler systems shall be further classified in accordance with table 110-10. 4) Standpipe systems shall be further classified as follows in accordance with table 110-11. Table 110-9 Fire Protection Systems — 2 Fire Protection System Definition Sprinkler system Includes express riser pipes that convey water to the laterals that supply sprinkler heads Standpipe system Includes bulk riser pipes equipped with hose connections, usually at each floor and roof, for exclusive use by the fire department; plus laterals on each floor of certain facilities that supply water to hose cabinets for use by the occupants to control fires until the fire department arrives. Combined system Includes bulk and express riser pipes that supply both sprinkler and sandpipe [standpipe] systems Table 110-10 Sprinkler System Classifications Class Description Class I Directly supplied from public water mains only, no pumps, tanks or reservoirs; no physical connection from other water supplies; no antifreeze or additives on [of] any kind; all sprinkler drains discharging to atmosphere, dry wells, or other Save outlets. Class II Directly supplied from public water mains, same as class I, except that authorization has been obtained for a booster pump to be installed in the supply line. Class III Directly supplied from public water mains, same as class I, plus one or more of the following: elevated storage tanks or pressure tank fire pumps taking suction from above ground covered reservoirs or tanks. All storage facilities shall be filled from the potable water supply and maintained in a potable condition. Class IV Directly supplied from public water mains, similar to classes I and II, and with an auxiliary water supply on or available to the premises; or auxiliary water supply located approximately 1,700 feet of the pumper connection. Class V Directly supplied from public water mains and interconnected with auxiliary supplies such as; pumps taking suction from reservoirs exposed to contamination on rivers and ponds, driven wells, mills or other industrial water systems, or where antifreeze or additives are used. Class VI Directly supplied from public water mains only, with or without gravity storage or pump suction tanks, and interconnected with industrial systems. Table 110-11 Standpipe System Classifications System Type Description Nonhazardous Impurities equal to class III and lower sprinklers Hazardous Impurities equal to class IV and higher sprinklers 5) Fire protection systems as defined by the International Fire Code shall be contained from the City of Canton Water System by backflow prevention devices that have approvals as required and are classified or listed by the Underwriters Laboratories and Factory Mutual Insurance as follows: a. Class I, II, III sprinkler systems and nonhazardous standpipe or combined systems shall be contained by the installation of a double detector check valve (DDC BFP). b. Class IV, V and VI sprinkler systems and hazardous standpipe or combined systems shall be contained by the installation of a reduced pressure zone detector check (RPDC BFP). c. Class systems with combination hazards shall be contained from the public water mains by procedures applicable to the component that requires the higher degree of protection. 6) Single detector checks that are used on nonhazardous fire protection systems class I, II, or III may not considered as a component part of a DDC BFP. Specifically, the addition of a second single check to one of these devices may not be substituted for a DDC assembly that is approved for backflow prevention. 7) It is intended that the approved DDC BFP be in lieu of, not in addition to, the checking devices already required by the Standard Plumbing Code in the supply to class I, or II, or the DCV BFP already required on class III nonhazardous systems, and that the approved RPDC be in lieu of the RPZ already required on hazardous systems. The only additional checking device intended is a three-quarter-inch DCV or RPZ BFP in the three-quarter-inch copper bypass line, in conjunction with the bronze detector meter. 8) The purpose of certain checking devices used, or likely to be used, with fire protection systems is given below to call attention to those that are approved for use as backflow prevention devices and those that are not. Table 110-12 Fire Protection System Checking Devices Approved for Use as Backflow Prevention Devices Item Device Description Approval A Directional Check To provide directional flow only Not an approved backflow prevention device B Alarm Check To signal an alarm, to summon the fire department, etc., when a sprinkler head flows water; and on wet-pipe systems to provide directional flow Not an approved backflow prevention device C Signal Detector Check To detect unauthorized use of water for other than fire service, to detect leaks in protection systems, and with bypass check to provide directional flow Not an approved backflow prevention device D Double Check Valve Assembly (DCV BFP) To prevent backflow of polluted water into potable water supply/system and to provide directional flow Approved for use on a dedicated service connection E Double Detector Check Valve (DDC BFP) To prevent backflow of polluted water from a fire protection system into a potable water supply/system, to detect unauthorized use of water, to detect leaks in the fire protection system and to provide directional flow Approved for use on a dedicated service connection F Reduced Pressure Zone (RPZ BFP) To prevent backflow of contaminated water into a potable water supply/system and to directional flow Approved for use on a combination service as in item (D) above G Reduced Pressure Zone Detector Check (RPDC BFP) To prevent backflow of contaminated water from a fire protection system into a potable water supply/system, to detect unauthorized use of water, to detect leaks in the fire protection system and to provide directional flow Approved for use on a dedicated service as in item (E) above 9) The shutoff valves required for periodic testing of the backflow prevention device shall be outside stem and yoke (OS&Y), FDA-approved fused epoxy coated inside and out, with resilient seats, and the inlet valve shall include an approved test cock on the upstream side. All components shall be listed for fire protections service by Underwriters Laboratories and Factory Mutual. The exception is that ball valves may be utilized for shut off means on pipe sizes below two inches as approved by the cross-connection program administrator. 10) The city has a designated cross-connection control program administrator. The program administrator shall coordinate and perform site inspections, provide customer notifications, and maintain all correspondence and records. The record system shall facilitate the monitoring of the following: a. Installation date of assemblies; b. Location of assemblies; c. Inspection and testing of assemblies; d. Performance of licensed testers; e. Calibration of testing devices. 11) Tasks to be performed annually: a. Update list of potential sources of contaminants and pollutants; b. Notify customers of testing requirements for installed backflow prevention devices; c. Update list of approved backflow devices and approved tests. D. Backflow prevention devices. 1) Selection. a. Backflow prevention devices shall be selected based on the degree of hazard assigned to the customer as follows: i. Those customers that are categorized under the health degree of hazard shall be required to install an approved reduced-pressure zone backflow-prevention assembly (RPZ) and have the device tested for proper operation annually. ii. Those customers that are categorized under the nonhealth degree of hazard shall be required to install an approved double check valve assembly (DCVA) and have the device tested for proper operation annually. b. Refer to the hazard assessment section (see subsection A above) of this section for guidelines regarding the selection of backflow prevention devices for particular customer types. c. Lawn sprinkler systems are open to the atmosphere and are not classified as a pressure type cross-connection. However, due to the special nature of the system, if no chemicals are injected into the system, the minimum protection against backflow shall include a double check valve assembly. If chemicals are injected or connections are made so that chemicals could be injected easily, minimum protection shall include a reduced pressure zone type backflow prevention device. d. Water being introduced into a vessel, tank, tanker truck, or miscellaneous other containers from any connection to the City of Canton Water System shall be through a method approved by the city engineer. Drawing 5 of chapter 112 of this UDC shows three approved methods for filling tanks. 2) Approval devices. a. All backflow prevention devices shall be approved in accordance with the applicable standards of the American Society of Sanitary Engineering, the American Water Works Association, and the University of Southern California Foundation of Cross Connection Control and Hydraulic Research. Final approval acceptable devices will rest with the program administrator. A list of approved devices is maintained by the Canton Engineering Department. b. If no standard yet exists for particular device, or if the device is a derivative on one covered by a national standard, the program administrator shall determine whether the device shall be allowed on the water service connection. 3) Installation of devices. a. The location of all backflow prevention devices shall be in an area that provides a safe working environment for testing and maintenance. The area shall be readily assessable, dry, and free from dirt, extreme cold or heat, and electrical hazards. b. Facilities that require a continuous, uninterrupted water supply shall install backflow prevention devices in parallel for testing and maintenance purposes. In no case shall a bypass arrangement be installed without approval of the cross-connection program administrator. c. Backflow prevention devices equipped with atmospheric vents, or with relief openings, shall be so installed and so located as to prevent any vent or any relief opening from being submerged. They shall be installed in the position as recommended by the manufacturer, and shall be protected from freezing. Illustrations of typical installations of backflow prevention devices can be found in chapter 112 of this UDC. The following guidelines shall govern the installation of backflow prevention devices: i. Backflow prevention device—Double check valve assembly (DCVA). This device shall not be buried in earth but may be installed below ground in a pit provided ball valve test cocks fitted where brass plugs are used. A positive shutoff valve shall be near the inlet and outlet sides of the device, and three ball valve test cocks provided on the device. A fourth test cock shall be provided on the upstream side of the inlet shut-off valve. When below ground, a union or flange shall be near the inlet and outlet sides. No intervening connections shall be between the shut-off valves and the backflow prevention device. ii. Backflow prevention device—Reduced-pressure zone assembly (RPZ). This device shall not be installed below ground. Where relief valve discharge could cause water damage, it shall be piped via an air gap, or a funnel, at the vent/relief port to a floor drain or other approved location. A positive shutoff valve shall be near the inlet and outlet sides of the device, and three approved test cocks provided on the device. A fourth test cock shall be provided on the upstream side of the inlet shutoff valve. A bronze strainer with 20-mesh stainless steel screen shall be included between the inlet shutoff valve and the device on sizes through two-and-one-half-inch. No intervening branch connection(s) shall be between the shutoff valves and the backflow prevention device. When the reduced pressure zone device is installed in a line subject to periodic no-flow conditions and the supply pressure is subject to fluctuations, an auxiliary directional check with soft disc, capable of functioning in any installed position of the RPZ, shall be provided between the inlet shutoff valve and RPZ head to lock the supply pressure in, and percent discharge through the vent/relief port. When a water pressure-reducing valve is required in the same line with the RPZ device, it is usually possible to locate the reducing valve upstream of the device and take advantage of the check valve effect of the reducing valve. In such case, the auxiliary directional check would be required. iii. Note: A thermal expansion control device shall be installed between a backflow prevention device and a water heater to limit the static pressure increase due to thermal expansion of the heated water. Providing and installing thermal expansion control device shall be the sole responsibility of the owner/occupant of the property. Testing procedures are outlined in the Manual of Cross-Connection Control, from the Foundation for Cross-Connection Control and Hydraulic Research published by the University of Southern California. d. Maintenance and testing of devices. i. Customers are responsible for maintaining backflow prevention devices in roper working order. Customers with RPZ and DCVA backflow prevention devices shall have the devices tested on an annual basis, or following repairs and/or clearing of devices. The city shall keep records of the testing, maintenance and repair of RPZ and DCVA backflow prevention devices and shall send out notices to customers when annual inspections come due. ii. Field testing and repair of these devices shall be by a person who is certified to understand the design and intended operation of backflow prevention devices. Tester must provide credentials of certification to the city for approval by the city. A list of approved testers is maintained by the Canton Engineering Department. E. Emergency notification procedures. 1) Initial signs of possible contamination of the public water system may be complaints from customers or direct notification from a customer knowledgeable of a contamination incident. 2) A cross-connection may contaminate only the customer's plumbing system. This is usually the case unless the pressure in the water distribution system is less than on the customer's property. Evidence of contamination may be discoloration of the water and/or the water may have an odor present. Although these are the simplest signs to look for, not all chemicals may be as easy to detect. 3) City personnel shall use the following notification and operation procedures in the event of a possible contamination to the water system. a. Required information. The following information will be obtained for transmission to the city manager and the cross-connection control program administrator by the first city employee either on the scene or receiving information of a contamination incident: i. Location, time, and date of incident. ii. Name of person(s) or company and phone number. iii. Name and phone number of person(s) with any information of incident. iv. Type of material involved, if known. v. Physical description of contamination. Color of water, odor, taste? b. Notification of city personnel. i. Notify city manager. ii. Notify cross-connection control administrator. iii. Notify building inspectors as needed. Building inspectors will be notified and requested to assist in locating the source of contamination. iv. Notify water treatment plant personnel. Water treatment plant personnel shall be notified as to the type of emergency, so that they may assist in the location, identification, and correction of any cross-connection which may affect the supply system. Laboratory personnel from the plant will be required to take samples of the contaminated water for analysis. c. Notification of EPD. i. Notify the Environmental Protection Division. ii. The emergency response program phone numbers are (800) 241-4113, (404) 656-4863 and (404) 656-6905. d. Notification of Cherokee County Department of Public Services. i. Notify health department personnel. ii. Health department personnel will be notified and requested to respond in the event of an emergency, so that they may assist with the identification and treatment of the contamination. e. Notification of the public. If an incident or emergency warrants public notification the following person(s) are authorized to make statements to the news media and shall be in charge of handling the emergency in the order listed: i. Mayor of the City of Canton; ii. City Manager of the City of Canton. 4) Operation procedures. a. Upon arrival on the scene, the extent of the contamination should be assessed. It should be determined whether the contaminant has entered the public water system or if it is still contained on a customer's premises. b. Service crew(s) shall be dispatched to the scene. Service crew(s) shall locate and turn off the customer's water service at the meter and fire line valves where the source of contamination is identified. Service crew(s) shall be prepared to close all necessary valves to isolate a section of the distribution system when instructed to do so. If the distribution system is contaminated, the contamination shall be contained in the smallest are possible. c. City personnel will personally notify each customer as the water service to each customer is shut off. Personnel from the police and fire departments may be required to assist in the notification of the Individual premises located within the affected area. The local paper and radio stations will be used when appropriate, as authorized by the city manager. d. A laboratory technician shall be dispatched to the backflow site. The laboratory technician shall collect the necessary samples and make provisions for further testing. e. Samples shall be taken to determine the type of contaminant and to what extent the contamination exists. Samples will be taken to the water system laboratory and may be sent to the state lab for identification. The city manager shall be kept informed of the results, so that the area of contaminated water can be isolated. Samples should be taken outside of the isolated area to ensure that the contaminant is contained. f. After the contaminant is identified, the cross-connection and the place of occurrence shall be located. All drinking fountains should be turned off. Water service shall be discontinued at the place of occurrence until an approved backflow prevention device is installed and tested. g. Service crews shall start flushing the water system upon the city manager's order to do so and shall continue flushing lines until lab tests show the contaminant to be at a safe level for human consumption. If necessary, the water mains will be resterilized using chlorine and/or treated with other chemicals to remove the residual effects of the contaminant. F. Public awareness. General methods that the city may use to inform its customers of the potential dangers from illegal and improper cross-connection include the following: 1) Written descriptions of potential cross-connection locations and the need to protect the public water system can be included as special interest articles for newspaper and local publications. 2) Providing speakers for civic clubs, political bodies and other functions. 3) Providing informational pamphlets to be distributed at schools and other locations. 4) Scrolling text messages about backflow prevention can be put on the government access channel of the local cable TV. 5) Public service announcements on local radio stations.