A. Generally. 1) Sewers shall be designed as separate sanitary sewers only in which rainwater from roofs, streets, and other areas and groundwater from foundation drains are excluded. 2) Overflows from sewers shall not be permitted. B. Design period. 1) Sewer systems should be designed for the estimated ultimate tributary population. Tributary population is considered to be all areas upstream of the discharge point of the system being designed. 2) Sewers will be designed and installed to the uppermost property line of the development being served. 3) Consideration shall be given to the maximum anticipated capacity of institutions, industrial parks, etc. C. Design factors. 1) In determining the required capacities of sanitary sewers, the following factors shall be considered: a. Maximum hourly sewage flow. b. Additional maximum sewage or waste flow from industrial plants. c. Ground water infiltration. d. Topography of the area. e. Depth of excavation. 2) New sewer systems shall be designed on the basis of an average daily flow of sewage of not less than 400 gallons per household per day. Sewers should be designed to carry the per capita flow when flowing one-half full. Normally, all sewers shall be designed with a peaking factor of not less than 2.5 and this may be increased upon the direction of the reviewing engineer. When deviation from the foregoing per capita rates is demonstrated, a description of the procedure used for design shall be included. D. Details of design and construction. 1) Size. No sewer shall be less than eight inches after leaving the uppermost property line to be served. 2) Depth. a. Any sewers installed in the street shall be sufficiently deep to provide five feet of cover at the inlet end of all service laterals at the street right-of-way, and over any part of the main or service within the street right-of-way. b. Any sewers on off street easements shall have a minimum of three feet of cover unless cast iron or ductile iron pipe is used. Filling over the pipe to obtain minimum cover is not allowed if the fill will impede the natural flow of surface water or will cause an erosion problem. 3) Slope. a. All sewers shall be so designed and constructed to give mean velocities, when flowing full, of not less than two feet per second based on Kutter's formula using an "n" value of 0.013. Table 111-2 lists the minimum slopes which should be provided; however, slopes greater than these are desirable: Table 111-2 Minimum Slope Requirements Pipe Diameter, inches Minimum Slope, ft/100-ft. 8 0.40 10 0.29 12 0.22 14 0.17 15 0.15 16 0.14 18 0.12 21 0.10 24 0.08 27 0.07 30 0.06 36 0.05 b. These minimum slopes will be used only when sufficient flows are expected to maintain a velocity of two feet per second and maintain a cleaning action in the line. Sewers shall be laid with uniform slope between manholes. Sewers on 20 percent slope or greater shall be cast iron or ductile iron pipe and shall be anchored securely with concrete anchors to prevent displacement by erosion or shock. Maximum slope of sewers shall be 30 percent and sewers shall be designed at less than 20 percent whenever possible. 4) Increasing size. When a small sewer is connected to a large one at a manhole, the connection shall not be lower than matching the 0.8 depth point of both sewers to the same elevation. For example, when connecting an eight-inch pipe to a 60-inch pipe a point 6.4 inches above the invert of the eight-inch pipe shall not be lower than a point 48 inches above the invert of the 60-inch pipe. Match crowns of the two pipes whenever possible. E. Gravity sewer pipe. 1) All sanitary sewer pipe up through 15-inch diameter must be polyvinyl chloride (PVC), ductile iron pipe (DIP), or steel pipe, except where DIP or steel pipe is designated. 2) For 18-inch diameter pipe and above, the contractor may have the option of using either high-density polyethylene (HDPE), PVC, reinforced concrete pipe (RCP), DIP or steel pipe, except where DIP or steel pipe is specifically shown on the plans. 3) All pipe shall be constructed with a minimum class "C" bedding.