--- title: Canton Zoning Ordinance, 111.03.05. Valve vaults collection: local-codes id: local-code:canton/zoning/111.03.05 cite_as: Canton, Ga., Zoning Ordinance § 111.03.05 canonical_url: https://georgiacommons.org/code/local/canton/zoning/111.03.05 md_url: https://georgiacommons.org/code/local/canton/zoning/111.03.05.md text_url: https://georgiacommons.org/code/local/canton/zoning/111.03.05/text source_url: https://library.municode.com/ga/canton date: 2026-11-11 status: active jurisdiction: city:canton jurisdiction_name: Canton place_fips: "1312988" corpus_version: local-codes-canton-bb716bdc4821 publisher: Georgia Commons, an independent project of Georgia Civic Data. Not the State of Georgia. Not legal advice. up: https://georgiacommons.org/code/local/canton/zoning/~part-iii/~chapter-111.md previous: https://georgiacommons.org/code/local/canton/zoning/111.03.04.md next: https://georgiacommons.org/code/local/canton/zoning/111.03.06.md index: https://georgiacommons.org/code/local/canton.md branch: zoning edition: As published by Municode, retrieved 2026-11-11 edition_date_kind: retrieved source_publisher: Municode version_id: local-code:canton/zoning/111.03.05@2026-11-11-5a2772fdba --- # Canton Zoning Ordinance, 111.03.05. Valve vaults > As published by Municode, retrieved 2026-11-11 > The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included. Part of: Part III - DEVELOPMENT CODE / Chapter 111 - DESIGN STANDARDS: SEWER SYSTEM TABLE OF CONTENTS A. Lift station check valves, isolation valves, and surge control valves (if required) shall be housed in a concrete valve pit adjacent to the lift station. Check valves provided shall be slow-closing check valves. Floor drain (three-inch diameter minimum) for the valve pit shall be provided and connected to the wet well. A P-trap shall be installed in the floor drain to block sewer gases from the wet well. Valve pits must be large enough for easy maintenance operations, with two feet to three feet clearance on all sides and with bottom of piping two feet to two feet six inches off of the concrete floor. Valve pits shall be no deeper than eight feet deep. Valve pits must have easy access. A hatch opening must be placed directly over the steps so that the steps are not recessed back away from the hatch opening. B. Acceptable manufacturers are as follows: 1) Check valves. a. Golden-Anderson. b. Crispin. c. Alternate acceptable to the city. 2) Isolation valves. a. Dezurik. b. Val-Matic. c. M&H. d. Alternate acceptable to the city. 3) Surge relief valves. a. Golden-Anderson. b. Alternate acceptable to the city. 4) Air release valves. a. Hawle. b. Alternate acceptable to the city. C. The discharge pipe inside the check valve vault shall be tapped for a discharge pressure gauge. The gauge shall be Ashcroft Type 1009 or alternate acceptable to the city, liquid-filled, three and one-half-inch dial, zero to 200 psi range with a diaphragm seal suitable for wastewater service. An isolation valve or corporation stop shall be installed on the tap to allow removal of the gage. D. All pipes in the valve vault shall be supported by either flanged pipe supports or concrete pier pipe supports. All piping in the valve vault shall be restrained using stainless steel threaded rod. E. A quarter turn plug valve shall be installed on the force main just outside the valve vault but within the chain linked fenced area of the lift station. Valve must be accessible by valve key. Valve port must be 100 percent of pipe diameter. Manufacturers shall be DeZurik 100 percent port eccentric (PEF), Val-Matic model 5600R 100 percent ported eccentric, or alternate acceptable by the city. ## History (Ord. No. 2014-18, § 2, 8-21-2014)