--- title: Canton Zoning Ordinance, 111.03.11. Emergency power requirements collection: local-codes id: local-code:canton/zoning/111.03.11 cite_as: Canton, Ga., Zoning Ordinance § 111.03.11 canonical_url: https://georgiacommons.org/code/local/canton/zoning/111.03.11 md_url: https://georgiacommons.org/code/local/canton/zoning/111.03.11.md text_url: https://georgiacommons.org/code/local/canton/zoning/111.03.11/text source_url: https://library.municode.com/ga/canton date: 2026-11-11 status: active jurisdiction: city:canton jurisdiction_name: Canton place_fips: "1312988" corpus_version: local-codes-canton-bb716bdc4821 publisher: Georgia Commons, an independent project of Georgia Civic Data. Not the State of Georgia. Not legal advice. up: https://georgiacommons.org/code/local/canton/zoning/~part-iii/~chapter-111.md previous: https://georgiacommons.org/code/local/canton/zoning/111.03.10.md next: https://georgiacommons.org/code/local/canton/zoning/111.03.12.md index: https://georgiacommons.org/code/local/canton.md branch: zoning edition: As published by Municode, retrieved 2026-11-11 edition_date_kind: retrieved source_publisher: Municode version_id: local-code:canton/zoning/111.03.11@2026-11-11-02c85686d0 --- # Canton Zoning Ordinance, 111.03.11. Emergency power requirements > As published by Municode, retrieved 2026-11-11 > The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included. Part of: Part III - DEVELOPMENT CODE / Chapter 111 - DESIGN STANDARDS: SEWER SYSTEM TABLE OF CONTENTS A. The minimum requirement for the provision of emergency power for lift stations shall be that each station shall be provided with an emergency generator capable of starting and running the appropriate number of pumps necessary to meet and/or exceed the maximum daily demand of the pump station and other ancillary devices. The generator shall be diesel powered with an automatic transfer switch (ATS) and provisions for an automatic exercise cycle. The contractor shall set the ATS transfer delay from utility to generator at a 30 second delay. B. The generator set shall be manufactured by Kohler, Cummins Onan, Katolight, Caterpillar or alternate acceptable to the city. C. The generator pad thickness shall be a minimum of 12 inches installed such that the bottom of the pad is six inches below grade and the top of the pad is six inches above grade. D. The person responsible for sizing the KW rating of the standby generator must supply a letter to the developer, contractor and city, stating that they guarantee the unit will operate the lift station pumps and other electrical demands with no greater than a 20 percent voltage dip. This letter must be signed and delivered before the day of scheduled start up. E. This specification defines the requirements for an emergency or standby electric generator set: 1) The generator set shall consist of an engine directly coupled to an electric generator, together with the necessary controls and accessories to provide electric power for the duration of any failure of the normal power supply. 2) The generator set shall have the following characteristics: a. Voltage: 480 VAC or 230 VAC. b. Phase: 3. c. Connection: Y. d. Wire: 4. e. Hertz: 60. f. Power Factor: 0.8. F. The generator set shall be capable of starting and running the necessary loads without exceeding the maximum voltage and frequency variations specified herein, or the maximum temperature limitations of the engine and generator. G. The horsepower rating of the engine shall take into account the generator efficiency and all parasitic losses such as fan, battery charger, etc. The generator set shall be capable of producing the required KW (without overload) for the duration of the power outage (standby rating), under the following ambient conditions: 1) Altitude, feet 1,000. 2) Ambient temperature range, zero degrees to one hundred degrees Fahrenheit. 3) Humidity at maximum ambient temperature, 80 percent. H. The following engine protective devices shall be provided, and an indicating light shall be supplied for use with each device specified: 1) Alarm system for high water temperature. 2) Alarm system for low oil pressure. 3) Automatic engine shutdown for high water temperature. 4) Automatic engine shutdown for low oil pressure. 5) Alarm and shutdown system for high water temperature. 6) Alarm and shutdown system for low oil pressure. 7) Engine over-speed automatic shutdown device. 8) Engine failed to start indicator light (over-crank). 9) Alarm for low coolant level. 10) A shunt trip and under-voltage trip shall be incorporated to cause the circuit breaker to open simultaneously with any automatic shutdown of the engine. I. A dual wall sub-base fuel tank shall be supplied with the generator set, which will allow the generator to operate continuously under pump load for 72 hours, but shall not exceed 1,000 U.S. gallons. The following requirements shall be met: 1) The tank shall be constructed of aluminized steel with all access ports and vents located on the top horizontal surface. 2) The tank shall be pressure and load tested according to U.L. 142 and shall be U.L. listed. 3) The tank shall be capable of supporting the weight of the generator, isolator, and enclosure, and shall have four lifting eyes capable of lifting the entire generator set package. 4) Low level and leak detector float switches shall be provided, both wired to control panel alarm lights, and a tank mounted fuel gauge. 5) The generator fuel storage tank shall be completely filled with fuel by the developer before start-up of the lift station and topped off after start-up. J. A generator main circuit breaker shall be provided. The interrupting capability shall be greater than the generator short circuit capability, but not less than 30,000 symmetrical amperes at 480 volts. The breaker continuous current trip rating shall be selected to provide overload protection for the generator. Main circuit breaker shall have GFCI protection per NEC. The breaker shall be provided with a shunt trip device. The generator starting circuit battery system will be used as the power source for the shunt trip circuit. The shunt trip coil voltage shall be suitable for use on the starting circuit. The breaker shall include three normally open and three normally closed auxiliary contacts. The breaker shall be a Square D Type MA, or alternate as manufactured by General Electric, Merlin Gerin, Eaton/Cutler-Hammer or alternate acceptable to the city. K. Automatic starting and stopping controls shall be furnished to start the engine automatically when the normal electric power fails or falls below specific limits and to stop the engine automatically after the normal power supply resumes. The signal for starting or stopping the engine shall be from an external auxiliary contact. The controls shall be capable of operating at 50 percent of normal DC system supplied voltage. L. It shall be possible to start the engine manually and run it unloaded by a manual pushbutton on the control cabinet that causes the engine to start, run and stop through the automatic start and stop controls. M. The following engine and generator instruments and controls shall be furnished and installed: 1) AC ammeter. 2) AC voltmeter. 3) Voltage adjusting rheostat. 4) Battery voltage meter. 5) Governor speed adjusting control. 6) Water temperature gauge. 7) Oil pressure gauge. 8) Manual start/stop control. 9) Manual-off-auto mode switch. 10) Voltmeter/ammeter phase selector switch. 11) Generator "run" status dry contacts (SCADA USE). 12) Common alarm dry contacts (SCADA USE). 13) Elapsed time meter. 14) Panel lights. 15) Indicator lights for engine alarm. 16) All wiring and interconnections shall be in accordance with commercial electrical standards. N. Weatherproof, sound attenuating, outdoor enclosure. 14-gauge steel construction. Includes two single access doors per side. Painted standard alkyd enamel finish. The city shall make the determination if the enclosure shall be sound attenuated for a commercial installation or residential installation. The city shall also make the determination as to the dBA level of attenuation required as each case may be unique. Sixty-five dBA at seven meters will be considered the standard starting point for attenuation. Exhaust roof dress cap, silencer mounting brackets, exhaust system assembly including the above mentioned silencer designed to go inside the enclosure with flex, elbow and rain cap. Painted standard alkyd enamel finish. Oil and water drains are extended to the exterior of the enclosure, each with identifying nameplate. 1) The enclosure shall be provided with the following electrical accessories: a. Junction boxes for battery charger and jacket water heater connection. b. Connection for low alarm, high alarm, leak alarm, and fuel fill pump switch. O. An engine block heater shall be provided to keep the engine coolant at a temperature of 85 degrees Fahrenheit with the ambient temperature. The heater shall be suitable for operation at 120 volts ac, single phase. External only; no internal elements shall be inside the engine. P. All generators sitting on fuel tanks must have a painted steel or aluminum "catwalk" all the way around the unit for service. Q. The system supplier shall furnish three sets of operating, maintenance and parts manuals covering all components for the generator set. The supplier shall also instruct the city in operation and maintenance of the unit. ## History (Ord. No. 2014-18, § 2, 8-21-2014)