Sec. 7.5-125. Material specifications.
About this text
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
All materials used in the work including equipment shall be new and unused materials of a reputable U.S. Manufacturer conforming to the applicable requirements of the Specifications, and no materials shall be used in the work until they have been approved by the City.
(1) Ductile iron pipe: Ductile iron pipe shall be designed in accordance with ANSI
A21.50 (AWWA C150), latest revision, and manufactured in accordance with ANSI A21.51 (AWWA C151), latest revision. Wall thickness class shall be a minimum Class 50.
Ductile iron pipe shall have an outside asphaltic coating per ANSI A21.51 (AWWA C151), latest revision. Pipe shall have standard cement lining inside with
asphaltic seal coat per ANSI A21.4 (AWWA C104), latest revision. Pipe shall be manufactured by American Pipe, US
Pipe, or McWane.
Pipe joints, except where restrained or flange joints are specified shall be push-on or mechanical joint type conforming to
ANSI A21.11 (AWWA C111), latest revision. Pipe shall be in eighteen (18) feet to twenty (20) feet nominal lengths with
standard deflection pipe sockets. Where restrained joints are shown or specified on pipe larger than twelve (12) inches
diameter the joints shall be "Fastite," "Lok-Ring," or approved equal. Restrained joints for pipe sizes twelve (12) inches diameter and smaller requiring restrained joint construction may utilize "Fast Grip" gaskets as manufactured by American
Pipe or an approved equal.
Where river crossing pipe is shown or specified, the pipe shall be "Flex-Lok Boltless Ball Joint Pipe" as manufactured by American Pipe or approval equal.
Where specified, flanged pipe shall meet ANSI A2 1.51 and be used with fittings
meeting ANSI A21.53 (AWWA C153).
(2) PVC Pipe: All PVC pressure pipe used for water mains shall be Class 200, DR 14
pipe rated at two-hundred (200) psi working pressure. All PVC pressure pipe proposed shall be two (2) inches diameter unless approved by the City.
(3) Copper tubing for water service: House service pipe shall be copper service pipe, type K, soft temper, seamless copper
tubing, conforming to Federal Specification WW-T-TOO. Compression joints shall be used. Pipe shall be one (1) inch service or three-quarters (�) inch service as
determined by the plans.
(4) Steel casing pipe: Steel casing pipe shall be steel pipe conforming to A.S.T.M
Designation A-139, Grade B, electric fusion welded steel pipe. The pipe shall have a minimum tensile strength of thirtyfive thousand (35,000) psi. both the exterior and interior of the pipe shall
have a coal tar varnishing coating. When crossing under railroad or GDOT road,
conform to agency specifications.
(5) Pipe fittings: Fittings shall be ductile iron furnished in accordance with ANSI
Specifications A21.53 (AWWA C153), latest revision, and shall have a minimum of two-hundred fifty (250) psi pressure
class rating. Joints shall be mechanical joint with ductile iron retainer glands
conforming to ANSI Specification A21.11 (AWWA C111), latest revision. Ductile iron retainer glands shall be Mega-Lug glands as manufactured by EBAA Irion.
All fittings shall be furnished with a cement mortal lining.
(6) Butterfly valves:
a. All butterfly valves shall be bubbletight closing at the rated pressure with flow in either direction, and
shall be satisfactory for applications involving throttling service and frequent operations or operations
after long periods of inactivity.
Valves shall meet the full requirements of AWWA Standard C504, latest revision for one-hundred fifty
(150) psi working pressure and shall be suitable for above ground or buried service.
All interior ferrous surfaces of valves larger than twelve (12) inch shall have a special epoxy coating meeting the requirements of AWWA C550.
Valve bodies shall be equipped with integrally cast mechanical join ends meeting ANSI A21.11 (AWWA C111).
Mechanical joints shall be fitted with retainer glands with set screws on ductile iron pipe. Retainer glands shall be Mega-Lug as manufactured by EBAA Iron.
Butterfly valves installed underground shall come equipped with the manual operator specified in the following paragraph.
b. Manual operators shall be of the traveling nut, self-locking type and shall be designed to hold the valve in any intermediate position between fully open and fully closed without creeping or fluttering. Operators shall be equipped with mechanical stop-limiting devices to prevent over travel of the disc in the open and closed positions. Valves shall close with a clockwise rotation. Operators shall be fully enclosed and designed for buried operation.
Provide extensions as necessary to bring the operating nut within eighteen (18) inches of the ground surface.
c. Manufacturer of butterfly valve and manual operator shall be preapproved by the City's water department before installation.
(7) Gate valves: Valves twelve (12) inches and smaller shall be gate valves. These
valves shall be non-rising stem design, iron body, bronze mounted with a compression, resilient seat manufactured in accordance with AWWA Standard C509,
latest revision. Vales shall be designed for a minimum working pressure of twohundred (200) psi and shall have two (2) inch square operating nuts, except in
meter vaults where handwheels shall be installed. Valves shall open when turner counter-clockwise and shall meet AWWA
specifications for Class C valves. Valves with flanged connections shall conform
to ANSUB16.1. Mechanical joints shall be Mega-Lug as manufactured by EBAA Iron. Gate valves shall be as manufactured by American Darling, Mueller, or M&H. Provide extensions as necessary to bring the operating nut within eighteen (18) inches of the ground surface.
Valves installed in eight (8) feet depth of cover shall have a manhole for
maintenance access.
(8) Valve boxes: Each valve shall be provided with a valve box. Valve boxes for valves shall be approved standard cast iron,
screw type adjustable-shaft boxes having a minimum shat diameter of five and one
quarter (5�) inches adjustable for the necessary depth. The casting shall be coated with two (2) coats of coal tar pitch varnish. The lids of all boxes shall bear the word "Water." Boxes shall be equal to Model 562-S with a five and one quarter
(5�) inch cast iron drop cover. All offpavement valve boxes shall have round concrete valve collars and valve markers.
(9) Air and vacuum relief valve assemblies:
Air and vacuum relief valves shall be cast iron body and covers with bronze trim, stainless steel float, Buna-N-Seal, and shall be designed for a minimum
working pressure of one-hundred fifty
(150) psi.
The valve shall be designed to exhaust large quantities of air during the filling period, and small quantities of air which collect in the line while operating under pressure.
Acceptable manufactures of air/vacuum valves are GA Industries, Inc., APCO or Val-Matic.
Valves between the water main and air relief valves shall be two (2) inch stainless steel ball valves.
All air and vacuum relief valves are to be installed in standard DFW-1200 plastic
meter boxes with cast iron meter box covers with proper read hole with gravel bottoms. Provide a minimum gravel layer
thickness of twelve (12) inches.
(10) Fire hydrants: All fire hydrants shall be designed and manufactured to comply
with the lates specifications of the AWWA.
They shall be designed for one-hundred fifty (150) pounds working pressure. The hydrants shall be of simple design, easy to operate, effectively and positively
drained and protected from damage by freezing, have bronze seat and drain ring and convenient for repairing and replacing parts.
Hydrants shall be equipped with one (1) four and one-half (4�) inch diameter pumper nozzle and two (2) two and onehalf (2�) inch diameter hose connections, which shall have threads meeting the latest requirements of the state fire insurance commission. Hydrants shall
have a three (3) way pentagonal operating nut, and shall open when turned counter-clockwise. Hydrants shall have a safety flange on the barrel and a safety coupling on the valve stem, to prevent
damage to barrel and stem in case of traffic accident. Hydrants shall be either Mueller Company's Centurion, M & H
Style 129 Traffic Model, or American Darling Mark 73-1.
The construction to the main line shall be with mechanical joint locked hydrant tee equal to American Cast iron Piper Company A-10180. All fire hydrant branches shall be valved. Wherever possible the fire hydrant shall be connected to the gate valve by using an anchor
coupling supplied by the same manufacturer as the hydrant. The -connection at the base of the hydrant shall be mechanical joint with ductile iron
retainer gland, for Class 150, centrifugally cast, six (6) inch ductile iron pipe. The valve opening shall meet the requirements of the AWWA Specifications for four and one-half (4�) inch hydrant. The valve, valve seat, and inner working
parts shall be easily accessible. The distance from the ground to the hose nozzle shall not be less than twenty-four
(24) inches. The body of each hydrant shall be neatly painted with a safety yellow reflecting paint and the ears and bonnet painted silver.
Each hydrant shall be tested to twohundred (200) psi. The first test shall be made with the valve closed. The second
test shall be made with the main valve open, but all nozzles closed. While this test is being carried on, the hydrant shall be subjected to a hammer test. Any
hydrant showing defects by leakage, sweating or otherwise shall be rejected.
The barrel and all parts shall withstand these tests. These tests shall be made in the field after the hydrants are installed.
All new developments shall require fire hydrant monitoring systems complying with the below criteria:
a. Fire hydrant must be completely and fully operational once the unit is installed. Unit does not require the need to shut water supply off, make modifications, and then recharge to obtain normal operation.
b. Pressure sensors must be located directly in the water supply line in the bottom plate of the hydrant main valve.
c. The supplied battery must have a minimum of two (2) year battery life when used with the factory default settings/parameters. Must not require power supply below grade.
d, Must not require Wi-Fi or Bluetooth for communication or operation.
e. Must have functionality across all platforms, desktop, laptop, tablet, mobile device or smart phone.
f. Must have hosted software, which is user friendly and allows end user/ client to migrate files directly from host to their water management software via CSV or Flat File to use with SCADA or similar utility infrastructure management software.
g. The device and all components must meet UL and ULFM requirements and have proper documentation to prove such.
h. Each new project requiring the installation of a new fire hydrant or relocation of an existing fire hydrant must include a minimum of one (1) remote pressure and temperature monitoring system. For projects requiring more than ten (10) hydrants two (2) in every ten (10) hydrants must include such technology. New projects will require a remote pressure/temperature
monitoring system in the front and back of the development, unless otherwise directed by the City water department.
i. Hydrant Technology is to be compatible with the McWane brand hydrants (Kennedy, M&H, and Clow)
or approved equal by the City water department. ·
(11) Service saddles: Service saddles shall be Ford F202 with CC threads (threequarters (3/4) inch single, one (1) inch dual.), Smith Blair Model 317, JCM Model 402, or Mueller.
(12) Pipe couplings: Pipe connections between new pipe and existing pipe shall be made with Dresser Style 90 long steel couplings for pipe sizes two (2) inches and below;
use mechanical joint sleeves for pipe sizes above two (2) inches. Field joints shall be made to ensure permanently
tight joints under all reasonable conditions of expansion, contraction, shifting, etc. Manufacturer shall be preapproved
by the City water department.
(13) Yokes: Yokes for three-quarters (3/4) inch services shall include iron bar Ford Y502P, ball valve Ford B94-223WR, dual check
valve Ford HHS91-323 Dual.
(14) Corporation stop: Corporation stop shall be Ford F1000 (three-quarters (3/4) inch single, one (1) inch dual).
(15) Branch piece: One (1) inch x threequarters (3/4) inch x seven and one-half (7�) inches Branch Piece shall be Ford
U48-43-7 1/2, one (1) inch compression joint inlet x three-quarters (3/4) inch MIP outlet.
(16) Meter boxes: The meter box shall be plastic, and the lid shall be cast iron. The meter box shall be as manufactured by
DFW; the lid shall be as manufactured by Kenflow.
(17) Tapping valves: Tapping valves shall be M.J. Type, two-hundred (200) psi
minimum rating, acceptable manufactures include Mueller, M&H, and American Darling.
(18) Tapping sleeves: Tapping sleeves shall be Ford Stainless Steel tapping sleeves with carbon steel flange appropriate for specific pressure rating. Model shall be preapproved by the City water department before installation.
(19) Water meters: The developer shall install the meter box and yoke on all residential and commercial and industrial services
in the three-quarters (3/4) inch and one
(1) inch sizes. The developer/owner shall be responsible for purchasing and providing the meter to the City. The City shall install the meter after service is applied for and all applicable fees are paid. On larger size commercial and industrial
services, the developer shall install the vault and all piping valves. No water
service will be provided until all required backflow prevention devices are in place and all relevant fees are paid.
(20) Backflow preventers: Backflow preventers for residential services shall consist of a dual check valve and shall be installed by the developer as part of the yoke
assembly. Backflow prevention devices for commercial services, as a minimum, shall consist of ASSE approved double check backflow preventer installed by the developer immediately downstream of the meter assembly. Contact the City water department backflow prevention coordinator for the specific determination of backflow prevention requirements.
(21) Valve markers: Developer shall use round concrete valve collars or concrete valve markers as directed by the City. Valve
markers shall be made of three-thousand (3,000) psi concrete and shall be four (4) feet long and four (4) inches on each side, with four (4) #4 reinforcing bars. The
markers shall be set with an even number of feet between the center line of the
valve and the center line of the aluminum disc in the top of the marker, and the
distance in feet between the valve and marker shall be stamped in the marker at the time of setting.
(22) Polyethylene encasement: Polyethylene film shall be manufactured of virgin
polyethylene material conforming to ASTM Standard Specifications D-1248-78 Type I, Class A or C, Grade E-1. The polyethylene film shall have a minimum thickness eight (8) mil. The polyethylene encasement material shall be provided in tube sized adequate for the various size pipes. Polyethylene encasement shall be
required at all locations within ten (10) feet of a gas main.
(23) Casing spacers for D.I.P. in steel casing:
Spacers shall be as manufactured by Cascade Waterworks Manufacturing Company or approved equal. Spacers for twenty-four (24) inch D.I.P. carrier pipe shall be CCS-2580 and eight (8) inches in width. Spacers for twelve (12) inch D.I.P carrier piper shall be CCS-1320 and eight
(8) inches in width. Spacers for eight (8) inch D.I.P. carrier shall be CCS-905 and eight (8) inches in width. All spacers
shall have a stainless steel shell. Spacers shall be located within two (2) feet of
each end of the casing and spaced no more than ten (10) feet apart within the casing. The positioning of the casing
spacers shall be centered for water mains.
History
(Ord. No. 44-24, § 1, 10-3-24)