(a) Pressure: All water mains, including those not designed to provide fire protection, shall be sized after hydraulic analysis to maintain a minimum pressure of 20 psi at ground level under all conditions of design flow. (b) Design flow: The design flow is to consist of projected peak demand plus fire flow (where applicable). To determine projected peak flow for residential developments, utilize values in Table 5.1. For developments other than residential, utilize AWWA "Manual of Water Supply Practices M22, Sizing Water Service Lines and Meters" to estimate peak demand. For fire flow, select proper value from Table 5.2. (c) Sprinkler connections: For each fire protection sprinkler connection to the City's water system, the developer must provide a double detector check valve installation consisting of not less than two detector check valves with by-pass meter on the second unit and two gate valves all enclosed in an accessible concrete or masonry pit. The pit is to have an aluminum access hatch.