Appendix C - DEVELOPMENT REGULATIONS PEAK WATER DEMANDS FOR RESIDENTIAL DEVELOPMENTS

Section 5.5. Location of water mains, fire hydrants and other fixtures.

About this text

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) Water Mains: Locate water mains along City or County streets on the south and west side of the street, five feet from the back of the curb or along ditch centerline where there is no curb. The minimum cover is to be 42 inches. Locate water service laterals with a minimum cover of 24 inches within street rights-of-way. Within 5 feet of the water meter, service lateral cover may be reduced to not less than 18 inches.

(b) Fire Hydrants Spacing: Provide fire hydrant spacing as requested by the Fire Chief and as follows:

(1) One and Two Family Residential (Zoning Districts R-12, R-7.52 and R-7.5): Space fire hydrants not more than 500 feet apart with additional fire hydrants located as necessary so that the maximum hose lay from a hydrant to the furthermost part of any building does not exceed 500 feet.

(2) Multiple-Unit Residential (Zoning District R-4): Space fire hydrant not more than 500 feet apart with additional fire hydrants located as necessary so that the maximum hose lay from a hydrant to the farthermost part of any building does not exceed 400 feet.

(3) Office-Institutional, Commercial and Industrial (Zoning Districts O-I, NC, HC, GC, II, and EI): Space fire hydrants not more than 300 feet apart so all portions of buildings can be reached by hose lays of not more than 300 feet.

(4) Central Business District (Zoning district CBD): Space fire hydrants not more than 300 feet apart so all portions of buildings can be reached by hose lays of not more than 300 feet.

(5) Parks, Education and Health (Zoning District PEH): Space fire hydrants not more than 300 feet a part so all portions of building can be reached by hose lays of not more than 300 feet.

(6) Planned Unit Developments (Zoning District PUD): Space fire hydrants as appropriate to the various component land uses of the Planned Unit Developments.

(7) Except when waived by the Fire Chief, a fire hydrant shall be located at all street intersections in all Zoning Districts.

(8) Locate fire hydrants between the water mains and right-of-way and within 5 feet of the right-of-way.

(c) Valves: Locate valves at not more than 1,000 foot intervals in residential areas and 500 foot intervals in non-residential areas. At water main junctions, the minimum number of valves to be provided shall equal the number of pipes extending from the junction minus one.

(d) Meters: Locate water meters in public rights-of-way within six inches of the right-of-way except where alternate location is approved by the public works department. water meters will be furnished and installed by the city upon payment of appropriate fees.

Read this code where it is posted (Municode) The source is the city's code as its publisher or its own website posts it. Check it there for later changes.