(1) All pre-owned manufactured homes moved into or relocated within Crawford County must bear an approval seal of either HUD or the Georgia Department of Community Affairs.

(2) Any pre-owned manufactured home to be moved into or relocated within the county must pass an inspection by the Building Official. This inspection will cover, but not be limited to:

a. Sanitary facilities.

1. Every plumbing fixture, water, and waste pipe shall be in sanitary working condition free from leaks or obstructions.

2. Both cold and hot water must be supplied.

3. Water heating facilities must be in safe working condition.

b. Exterior condition.

1. Every habitable room shall have at least one window that can be opened facing directly to the outdoors.

2. The exterior of the home shall be free of loose or rotting boards or timbers and any other conditions that might admit rain or moister to the interior portions of the walls or to the occupied spaces.

3. The exterior siding shall be free of rot and rust and must be uniform in appearance.

4. Roofs shall be structurally sound and have no obvious defects, which might admit rain or cause moisture to collect on the interior portion of the home.

c. Safety of operating systems (electrical, heating, etc.), including:

1. Heating facilities should operate in a safe, working condition.

Where a central heating system is not provided, each manufactured home shall be provided with facilities whereby a heating appliance may be connected.

2. Unvented fuel burning heaters shall be prohibited except for gas heaters listed for unvented use and the total input rating of the unvented heaters is less than thirty (30) BTU per house per cu. Ft.

of room content.

3. Unvented fuel burning heaters shall be prohibited in bedrooms.

4. Distribution panels shall be in compliance with the approved listing, complete with required breakers or fuses, with all unused openings covered with blank covers approved and listed for that purpose. Connections shall be checked for tightness. Panels shall be accessible.

5. Electrical systems (switches, receptacles, fixtures, etc.) shall be properly installed, wired and shall be in working condition. The home shall be subjected to an electrical continuity test(s) to assure that all metallic parts are properly bonded.

d. The presence of operable smoke detectors.

e. Interior condition:

1. Every floor, interior wall and ceiling shall be in sound condition.

2. Condition and operability of doors and windows, and

8.1.4.3. Timing of Inspection

(1) For a pre-owned manufactured home being relocated from any site within the county, whether incorporated or unincorporated, the inspection shall be conducted prior to moving the home from the site. If the home has already been moved to the site, the inspection must be conducted prior to connecting the manufactured home to a water supply, to a sanitary disposal system, and to permanent power.

(2) For a pre-owned manufactured home being moved into the county from another county or state, the inspection shall be conducted at the new home site prior to connecting the manufactured home to a water supply, to a sanitary waste disposal system, and to permanent power.