Sec. 32-367. Requirements for interceptor and specific plumbing connections.
About this text
- As published by Municode, current through 2020-02-10
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) All food service establishments shall only introduce pretreated wastewater acceptable to the county under the requirements and standards established herein before discharging, directly or indirectly, into any county sewer system.
(b) No more than 100 mg/l of FOG shall be discharged per operating business day. The FOG generator shall bear all of the expense of proving compliance with the 100 mg/l threshold.
(c) Any food service establishment required to provide FOG pretreatment shall install, operate, and maintain an appropriately designed and adequately sized FOG interceptor that has
been approved by the county.
(d) The testing procedures for waste constituents and characteristics shall be as provided in
40 CFR 136.
(e) FOG interceptors shall be connected to the food service establishment's lateral sewer line after all fixtures which may introduce FOG have been connected and shall have fresh air connected, as defined in these regulations. Freshair fixtures include, but are not limited to, sinks, dishwashers, garbage disposals, automatic hood
wash units, floor drains in food preparation and storage areas, and any other fixtures which have a potential to introduce FOG. Wastewater from sanitary sewer fixtures and other similar fixtures shall not be introduced into the FOG interceptor.
(f) FOG interceptors shall not be connected to septic tanks.
(g) All food service establishments that have dumpster pad/trash compactor drains on site and are connected to the sewer system shall have a separate interceptor (no less than 1,000 gallons in size) installed and functioning at all times. The sloping area to the outside drain and the drain shall be covered either by the dumpster/ compactor or a canopy to prevent inflow and infiltration of rainwater.
(h) Any drains that lead to the sewer system including, but not limited to, trench drains, enclosed dock drains, carwash drains, elevator drains, and other similar types of drains shall
have an oil-water debris interceptor of no less than 1,000 gallons and no more than 3,000 gallons in capacity.
History
(Comp. Ords. 2008, ch. 25, art. III, div. 5.1, § 6)