Sec. 80-194. Utility substations (telephone, electric, or gas, etc.).
About this text
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) Allowable districts: All.
(b) Standards:
(1) Utility substations measuring less than 35 square feet and less than five feet in height from finished grade are exempt
from these regulations.
(2) All substation structures shall be contained within the boundaries of the subject parcel and meet the minimum development standards of the district unless otherwise required in this article section.
(3) Minimum setback of all utility structures from a residential structure shall be:
a. Electric—200 feet.
b. Gas and telephone—the applicable minimum setback for the district in which located.
(4) A minimum ten-foot wide landscape strip planted to buffer standards shall be
required around the perimeter of all utility sites except along lines where buffers are required.
(5) For electric substations, provide a minimum 50-foot wide replanted or natural buffer adjacent to the property lines of any residential district and/or the AG district used for single family.
(6) Interior to landscape strips or buffers that do not accomplish 100 percent visual screening as defined in the tree protection and landscaping ordinance, provide an eight-foot high opaque fence or,
masonry wall, a minimum four-foot high landscaped earthen berm, a vegetative screen or some combination thereof, subject to the approval of the planning and zoning department.
(Ord. No. 2012-04, § 1(Exh. A), 6-11-2012; Ord.
of 10-28-2019(1))