Gordon County · Zoning Ordinance

Chapter 3 - PROTECTION OF NATURAL FEATURES AND RESOURCES

3.01.18. Specific Standards

About this text

  • As published by Municode, current through 2024-03-19
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

In all areas of special flood hazard the following provisions are required:

A. New residential construction and/or substantial improvements. Where base flood elevation data are available, new construction and/or substantial improvement of any residential structure or manufactured home shall have the lowest floor, including basement, elevated no lower than one (1) foot above the base flood elevation. Should solid foundation perimeter walls be used to elevate a structure, openings sufficient to facilitate equalization of flood hydrostatic forces on both sides of exterior walls shall be provided in accordance with standards of subsection

(C) of this section. All heating and air conditioning equipment and components (including ductwork), all electrical, ventilation, plumbing, and other service facilities shall be elevated at or above one (1) foot above the base flood elevation.

B. Nonresidential construction. New construction and/or the substantial improvement of any structure located in A1—30, AE, or AH zones, may be flood-proofed in lieu of elevation. The structure, together with attendant utility and sanitary facilities, must be designed to be water tight to one (1) foot above the base flood elevation, with walls substantially impermeable to the passage of water, and structural components having the capability of resisting hydrostatic and hydrodynamic loads and the effect of buoyancy. A registered professional engineer or architect shall certify that the design and methods of construction are in accordance with accepted standards of practice for meeting the provisions above, and shall provide such certification to the official as set forth above and in Section 3.01.16(G).

C. Elevated buildings. All new construction or substantial improvements of existing structures that include any fully enclosed area located below the lowest floor formed by foundation and other exterior walls shall be designed so as to be an unfinished or flood resistant enclosure. The enclosure shall be designed to equalize hydrostatic flood forces on exterior walls by allowing for the automatic entry and exit of floodwater.

1. Designs for complying with this requirement must either be certified by a professional engineer or architect or meet the following minimum criteria:

a. Provide a minimum of two (2) openings having a total net area of not less than one (1) square inch for every square foot of enclosed area subject to flooding;

b. The bottom of all openings shall be no higher than one (1) foot above grade;

and

c. Openings may be equipped with screens, louvers, valves or other coverings or devices provided they permit the automatic flow of floodwater in both direction;

2. So as not to violate the "Lowest Floor" criteria of this section, the unfinished or flood resistant enclosure shall only be used for parking of vehicles, limited storage of maintenance equipment used in connection with the premises, or entry to the elevated area; and

3. The interior portion of such enclosed area shall not be partitioned or finished into separate rooms.

D. Standards for manufactured homes and recreational vehicles where base flood elevation data are available.

1. All manufactured homes placed, and/or substantially improved, on individual lots or parcels, in expansions to existing manufactured home parks or subdivisions, in new and/or substantially improved manufactured home parks or subdivisions, or on a site in an existing manufactured home park or subdivision where a manufactured home has incurred "substantial damage" as the result of a flood, must have the lowest floor including basement, elevated no lower than one (1) foot above the base flood elevation.

2. All manufactured homes placed and/or substantially improved in an existing manufactured home park or subdivision must be elevated so that:

a. The lowest floor of the manufactured home is elevated no lower than one

(1) foot above the level of the base flood elevation, or

b. The manufactured home chassis is elevated and supported by reinforced piers (or other foundation elements of at least an equivalent strength) of no less than thirty-six (36) inches in height above grade.

c. All manufactured homes must be securely anchored to an adequately anchored foundation system to resist flotation, collapse and lateral movement.

3. All recreational vehicles placed on sites must either:

a. Be on the site for fewer than one hundred eighty (180) consecutive days, or

b. Be fully licensed and ready for highway use, (a recreational vehicle is ready for highway use if it is licensed, on its wheels or jacking system, attached to the site only by quick disconnect type utilities and security devices, and has no permanently attached structures or additions), or

c. The recreational vehicle must meet all the requirements of Section 3.01.18(A) including the anchoring and elevation requirements of Section 3.01.18(D)(2)(c), above.

E. Floodways. Located within areas of special flood hazard established in Section

3.01.06 are areas designated as floodways. A floodway may be an extremely hazardous area due to velocity floodwaters, debris or erosion potential. In addition, the area must remain free of encroachment in order to allow for the discharge of the base flood without increased flood heights. Therefore, the following provisions shall apply:

1. Encroachments are prohibited, including earthen fill, new construction, substantial improvements or other development within the regulatory floodway.

Development may be permitted however, provided it is demonstrated through hydrologic and hydraulic analyses performed in accordance with standard engineering practice that the encroachment shall not result in any increase in flood levels or floodway widths during a base flood discharge. A registered professional engineer must provide supporting technical data and certification thereof.

2. If subsection (E)(1) of this section is satisfied, all new construction and substantial improvements shall comply with all applicable flood hazard reduction provisions of this section.