Chapter 6 - INFRASTRUCTURE IMPROVEMENTS

6.03.03. Fire Protection

About this text

  • As published by Municode, current through 2024-03-19
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

A. Fire protection. The placement of fire hydrants within a subdivision or parcel of land deemed necessary for the protection of buildings, homes, facilities, or other property types shall be required, with hydrant placement at locations such that each structure is not further than five hundred (500) feet from such hydrant. When six-inch public water lines are available within one thousand (1,000) feet from any portion of the subdivision, the developer/property owner shall assume all costs of extending such lines to the subdivision such that no structure within the subdivision is more than five hundred (500) feet from a hydrant. Refer to the current edition of the International Fire Code, Appendix B, for minimum fire-flow requirements.

B. Location of hydrants.

1. Subdivisions. All fire hydrants will be placed within five hundred (500) feet of each structure, as determined by the fire inspector, at the time of plan review for the construction plat.

2. Industry and business. The location, number and distribution of fire hydrants will be determined by the fire inspector, referencing the current edition of the International Fire Code, Appendix.

C. Water line size. All fire hydrants will be installed on water lines no less than six (6) inches in diameter, unless approved by the fire chief. Fire-flow requirements will dictate the actual water line to be installed.

D. Fire hydrant type. All fire hydrants shall be Mueller brand, Super-Centurion 250, Number A-423, 3-way hydrants. All shall include two and one-half-inch hose outlets and one (1) five-inch Storz Connection.

E. Inspection. Notification shall be made by the developer to the fire inspector after installation of fire hydrants has been completed. All installations shall meet N.F.P.A.

24 and 25 requirements, with completed inspection and test reports provided to the fire inspector before the final plat is submitted. The fire inspector will inspect the hydrants to ensure proper bury depth, location, and usability.

History

The history line the source prints at the end of the section.

(Ord. of 2-25-20(1))

Read this code where it is posted (Municode) The source is the city's code as its publisher or its own website posts it. Check it there for later changes.

Version local-code:gordon-county/zoning/6.03.03@2024-03-19-beb26c54fe

The assistant can say what this section says in this edition, quoting it and linking to it. It will not apply the law to your situation, and nothing here is legal advice.

Gordon County Zoning Ordinance, 6.03.03. Fire Protection | Georgia Commons