Lee County · Zoning Ordinance
Part II - CODE OF ORDINANCES / Chapter 38 - LAND DEVELOPMENT CODE / Article X - POTABLE WATER REQUIREMENTS / Division 1 - GENERALLY
Sec. 38-448. Water line design criteria.
About this text
- As published by Municode, current through 2026-06-23
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) Working pressure. All pipe, fittings, valves, fire hydrants and appurtenances shall be capable of full service at a working pressure of not less than 150 psi.
(b) Pressure. All water mains including those not designed to provide fire protection, shall be sized after hydraulic analysis to maintain a minimum, in service pressure of 20 psi at ground level under all conditions of design flow.
(c) Design flow.
(1) The design flow is to consist of projected demand plus fire flow (if required). To determine projected peak flow for residential developments the values in Table 6.3A shall be used. For developments other than residential, utilize AWWA. Manual of Water Supply Practices M22. Sizing Water Service Lines and Meters, to establish peak demand. For fire flow, select the proper value from Table 6.3B.
(2) Any new water lines connected to a utilities authority water main with pressure supplied by an elevated tank shall be required to design for fire flow.
Table 6.3A Peak Water Demand for Residential Developments Number of Dwelling Units Gallons per Minute per Dwelling Unit 5 8.0 10 5.0 20 4.3 30 3.8 40 3.4 50 3.0 60 2.7 70 2.5 80 2.2 90 2.1 100 2.0 150 1.6 200 1.3 300 1.2 400 0.9 500 0.8 750 0.7 1,000 0.6 Table 6.3B Minimum Design Fire Flows Zoning District Gallons per Minute R-1 750 R-2 1,000 Zoning District Gallons per Minute R-3 750 C-1 750 C-2 1,000 I-1 1,250 I-2 1,250 (Ord. of 9-18-00(2), § 38-448)