(a) Any pipe, solder or flux used in the installation or repair of the water lines must be lead free. Pipes and fittings must no contain more than eight percent lead and solders and flux must not contain more than 0.2 percent lead.
(b) Pipe and fittings.
(1) Ductile iron pipe shall be centrifugally cast with minimum wall thickness as follows.
Nominal Diameter (inches) Wall Thickness (inches) 6 0.25 8 0.27 10 0.29 12 0.31 16 0.34 18 0.35 20 0.36
(2) The project sponsor shall submit certification to the authority or its agent that the soil along the route of the proposed pipeline had been analyzed and evaluated in accordance with AWWA C105, pages 4-7 of Appendix A and that the soil will not be corrosive to ductile iron pipe. In areas where soil is corrosive to ductile iron pipe the pipe shall be covered with a sealed polyethylene sheath as hereinafter described in these specifications.
(3) The pressure rating, metal thickness, net weight of pipe without lining, length of pipe, name of manufacturer and letters "DI" shall be clearly marked on each length of pipe.
(4) If it is necessary to cut ductile iron pipe, in no case shall it be cut by burning, but shall be cut by saw, cutter, abrasive wheel or other approved means.
(5) In areas where it is shown that soil will be corrosive to ductile iron pipe, the pipe shall be covered and sealed with a polyethylene sheath.
a. Polyethylene sheath shall be class "C" in accordance with AWWA specification C105.
b. Where polyethylene sheath is placed on pipe, the trench shall be backfilled to a depth of not less than one foot above the top of the pipe with sand or sand-clay backfill. Sand or sand-clay backfill shall be specially selected from the excavation and shall contain no stumps, roots, rocks or other items that will puncture sheathing.
(6) Flexible joint pipe. Flexible joint pipe shall meet the requirements of AWWA C151 for ductile iron pipe and may be of the bolted or boltless type suitable for 150 psi working pressure. If bolted type pipe is used all bolts shall be corten steel. All pipe and fittings shall meet the applicable requirements AWWA C151. The interior and exterior of all pipe and fittings shall receive an approved bituminous coating, except the ball and machined surfaces which shall receive a protective coating as recommended by the manufacturer. The interior of all pipe shall be cement mortar lines as specified in
AWWA C104.
(7) PVC pipe for water lines. Pipe joints shall be integral bell and spigot type with rubber ring sealing gasket. The pipe bell shall be designed to be at least as strong as the pipe wall. Standard lengths shall be 20 feet except that 15 percent of total footage for a particular project may be random lengths of not less than ten feet each. Each pipe shall be tested by the manufacturer to 600 psi for a minimum of five seconds. The bell shall be tested with the pipe. All pipe shall be listed by the Underwriter's Laboratories, Inc.
and by Factory Mutual as approved for use in underground municipal water distribution systems and private fire protection systems. Cast iron or ductile iron fittings shall be used with PVC pipe. Cast iron or ductile iron fittings shall meet the requirements of subsection (b)(10) or (11) of this section.
(8) All PVC water mains shall be marked with a locating wire to provide a means of locating PVC water mains using standard pipe location equipment. Locating wire shall be a minimum of # 8 copper or aluminum wire suitable for underground burial and shall be placed within three inches of pipe for the entire length of main. Intermediate in depth between the PVC water main and ground surface, non-metallic water main warning tape is to be placed during the process of backfilling the ditch line.
(9) Pipe for service connections. Connections from the corporation stops to the house services shall be type K annealed copper tubing with flared fittings, or 160 psi polyethylene per ASTM D2239 with SS compression fittings or "Insta-Tite" fittings by Mueller. Polyethylene is not approved for use near existing or potential future manuAPPENDIX C—LAND DEVELOPMENT REGULATIONS § 10.11 facture, use, storage, or disposal of petrochemicals. Where polyethylene is used, fittings shall be used for all vertical bends of more than 221
/2 degrees, and special attention shall be given to assure proper bedding.
(10) Cast iron fittings shall be mechanical joint and shall conform to AWWA C110 for sizes six-inch through 12-inch and shall be class 250. Fittings 14 inches and larger shall be class 150 and shall be of the dimensions and metal thickness as shown in the Handbook of Ductile Iron Pipe as published by the Ductile Iron Pipe Research Association. All fittings shall be cement mortar lines in accordance with AWWA C104 including an approved bituminous seal coat.
(11) Ductile iron fittings shall be designed for pressure rating of 250 psi and shall be in accordance with AWWA C110. Fittings shall be mechanical joint. All fittings shall be cement mortar lines in accordance with AWWA C104 including an approved bituminous seal coat.
(c) Backflow preventers shall be required. Use reduced pressure type suitable for 150 psi working pressure and complying with ASSE 1013 and AWWA C506 specifications. Use flanged cast iron body with bronze trim. Developer shall furnish complete unit including preventer, strainer and test cocks.
(d) Gate valves.
(1) Twelve inches and smaller: Each valve shall have mechanical joint bell ends. Valve shall be for horizontal mounting and valve stem shall be furnished with two-inch square water works nut. Resilient seat gate valves are acceptable.
(2) Fourteen inches and larger: Each valve shall have mechanical joint bell ends. Valves shall be for horizontal mounting and shall be provided with bypass valve with two-inch square operating nut. The main valve shall be provided with watertight bevel gear case with outside, packed stuffing box with a gland enclosure. Both main valve stem and pinion stem shall be provided with accessible alemite connections. The test plug in each main valve shall be provided with a brass gage cock with handle lever.
(e) Butterfly valves.
(1) Butterfly valves shall be rubber seated for 150 psi, minimum working pressures and line velocities up to 16 fps. The bodies of all valves shall be cast iron construction of ASTM A126, Class B or ASTM A48, Class 40. Valves shall be manufactured by a company acceptable to the manager of development services. Underground valves shall be provided with operators with non-corrosion construction for input shafts, seals, bushings, and bolting. Operators shall be totally enclosed and permanently lubricated for direct burial of the valves and frequent submergence in water up to 20 feet of head. The operators shall open the valves on a counter-clockwise rotation of the operator wrench nut which shall be AWWA two-inch, square cast iron. The valve ends shall be mechan-ical joint in accordance with AWWA C111. Except as modified herein, the butterfly valves and operators shall meet or exceed the applicable requirements of the Specifications for Rubber Seated Butterfly Valves, AWWA C504 for Class 150B.
(2) All butterfly valves shall be provided with O-ring seals, nonadjustable stuffing boxes and shall be of a self-sealing or self-adjusting type that can be replaced without the necessity of removing the valve or the valve shaft from its pipeline location.
(3) The valves shall be installed with the valve shaft in a horizontal position. The shaft shall be of 18-8 stainless steel, type 304. A machined, one piece, high tensile steel, hexagonal shaft fitting a matching opening through the valve disc, completely sealed from the pipeline contents with type 304 stainless steel bushings is acceptable. Valve discs shall be keyed or pinned securely to the valve shaft. Pins, wedges, and accessories shall be 18-8 stainless steel, type 304 or 316.
(4) Valve discs may be made of ASTM A536, Ni—Resist Type 1 ductile iron or ASTM A48 Class 40 cast iron.
(5) Valve seat surfaces shall be 18-8 stainless steel, type 304 or Monel, or Ni-resist on natural rubber or an approved equal.
(f) Fire hydrants.
(1) Hydrants shall be of the same general type as hydrants in the existing system. Barrels of hydrants shall be designed to permit installation of one or more extension sections to increase the depth of bury of the hydrant.
(g) Encasement pipe.
(1) Encasement pipe shall conform to AASHTO standards and the state department of transportation standards where being placed under roads and to AREA 1-5-B where placed under railroads. Encasement pipe shall be installed by a dry boring method in which the casing pipe is placed simultaneously with the boring action. Inspect the roadway or track directly above the work before, during and after the placing of the encasement for settlement. If settlement occurs the contractor shall bring the roadway surface to its original grade by means approved by the state department of transportation or realign the track to its proper grade by means approved by the track owner.
(2) Corrugated metal encasement pipe shall be the size, section modulus and type required and shall conform to AASHTO designation N-36-60. The pipe shall be bituminous coated inside and outside in accordance with AASHTO designation M-190-60, type A.
(3) Welded steel encasement pipe shall be of the size and wall thickness required and shall conform to ASTM designation A-252, Grade 2. The pipe shall be coated on the outside only with a coal tar primer coat followed by a single application of hot coal tar enamel 3/32 inch thick plus a 1/32 inch, bonded 15 lb. asbestos felt wrap or approved equal. At the option of the contractor, uncoated pipe may be used subject to the approval of the City of Leesburg, the Georgia Department of Transportation or the railway company provided the wall thickness is at least 0.063 inch greater than coated pipe.
(h) Corporation and curb stops.
(1) Corporation stops shall be Mueller No. H-9971, H-15009 or equals from Hays, McDonald, Ford or Jones.
(2) Curb stops shall be Mueller No. H-15175, H-15211, or H-15171 or equals from Hays, McDonald, Ford or Jones.
(i) Miscellaneous materials.
(1) The threaded rods and clamps for anchorage shall be mild steel conforming to ASTM A-36. The rods and clamps shall be brushed clean of all rust and foreign matter and completely coated with "no-oxide" or an approved equal before backfilling.
(2) Anchoring couplings shall meet the requirements set forth for cast iron or ductile iron fittings.
(3) Locked mechanical joint retainer glands shall be ductile iron retainer glands equipped with the hardened cupped and set screws. Assembly shall be designed for a minimum pressure or 250 psi. Retainer gland screws shall be tightened as recommended by the manufacturer.
(4) Tapped valves and sleeves shall meet the requirements set forth for gate valves. Tapping sleeves shall be all stainless steel or ductile iron construction.
(5) The minimum compressive strength required for formed concrete at 28 days is 3,000 psi.
(6) All stone for riprap shall consist of rough, unhewn quarry stone weights not less than 165 pounds per cubic foot as nearly rectangular in section as possible. The stone shall be resistant to the action of air, temperature changes and water. It shall be sound and dense and suitable in all other respects for the purpose intended.
a. A six-inch thick blanket of slag or gravel shall be placed as a bed for riprap. Slag or gravel shall be as hereafter specified.
b. Riprap shall be placed in such a manner as to ensure that the larger pieces are distributed uniformly and that the smaller pieces will fill the spaces between the larger pieces. After placing the riprap it shall present a reasonably smooth surface to the thickness.
c. After riprap is in place the voids shall be completely filled with clean gravel or slag.
The gravel or slag shall be worked into the crevices between the rocks with rodding or other approved methods.
(7) Gravel or slag shall be screened, washed and shall be 100 percent retained by the one-quarter-inch screen. One hundred percent shall pass a one-inch opening and shall be uniformly graded from maximum size to minimum size. Foreign matter shall not exceed three percent by weight when dry.
(8) Geotextile fabrics shall be as designated on the plans and approved by the manager of development services.
(j) Iron pipe corrosion.
(1) Submit certification to the manager of development services that the soil along the route of the proposed pipeline has been analyzed and evaluated in accordance with AWWA C105 and that the soil will not be corrosive to ductile iron pipe.
(2) Where polyethylene sheath is placed on pipe, the trench shall be backfilled to a depth of not less than one foot above the top of the pipe with sand or sand-clay backfill. Sand or sand-clay backfill shall be specially selected from the excavation and shall contain no stumps, roots, rocks, or other items that will puncture sheathing.