(a) All commercial, industrial, and institutional sites shall have a dumpster pad and paved access provided for the removal of refuse from the property. The utility billing supervisor shall determine the appropriate size of the refuse receptacle. The size requirements for the receptacle shall be determined based upon the proposed business and the intended use. The refuse receptacle requirements shall be incorporated in the site plan submitted to the city manager of development services for review. The following applies to all types of businesses: (1) The dumpster pad and approach shall meet the following requirements: a. The pad shall be made of concrete measuring six inches thick and having a minimum compressive strength of 4,000 psi at the 28-day break. b. The minimum dimensions of the concrete pad shall measure 20 feet, six inches long by 12 feet, six inches wide. (2) The dumpster receptacle enclosure shall consist of three walls and a front gate. The walls and gate shall meet the following requirements: a. The minimum measurements for the interior of the walled enclosure shall be ten feet deep and 11 feet wide. b. The walls shall be eight feet high or at least 24 inches above the top of the dumpster receptacles. c. All forms of business other than food establishments have the option of using masonry block, wood, or other suitable material for the construction of the walls to enclose the dumpster receptacle. d. An opaque front gate shall be installed to provide containment of loose trash and to provide for concealment of the refuse receptacle. e. A minimum of three six-inch diameter pipe bollards spaced two feet apart (on center) and 18 inches (on center) from the rear wall of the enclosure shall be installed to protect the rear wall from damage. The bollards shall be filled with concrete. They shall be seven feet in length with three feet set below finished grade and four feet above finished grade. The three feet of the bollard set below finished grade shall be encased in concrete. The concrete easement shall measure at least 18 inches in diameter and shall extend a minimum of four inches below the bottom of the metal casing of the pipe bollard. Paint all bollards OSHA yellow. f. Each section of the access gates shall swing open a full 120 percent from the closed position. A pipe bollard shall be installed for each section of gate at the full open position to restrict the gate from opening further. Bollards shall meet the same requirements for installation as stated in section 9.13(a)(2)e. g. The gates shall have three-fourths-inch diameter by one and one-half-inch deep recesses formed in the concrete and asphalt for the gate cane bolts to fit in. Provide two each at gate in closed and open positions. Field verify the exact locations. h. An optional three-foot-wide access gate in the side wall of the enclosure may be provided for employees to gain access to the enclosure to facilitate the emptying of trash receptacles. For food establishments the following additional requirements apply: i. The walls for dumpster pads at food establishments shall be made of masonry brick or block material only. j. To provide for the washdown of trash containers there shall be a sump with a grate inlet within the confines of the walled dumpster enclosure. The inlet shall be connected to an approved drain pipe that is directly connected to the sanitary sewer line leading either to an approved septic drain field or an approved public sanitary sewer system. k. To reduce the amount of rain water run-off from entering the sanitary sewer system through the sump grate inlet the concrete pad shall be designed so that the rain water from the surrounding parking lot does not enter the enclosure. This may be accomplished by raising the concrete pad above the adjacent parking lot grade or, by sloping the pad to shed stormwater away from the front opening of the enclosure. Spot elevations shall be shown for the dumpster pads. (3) Appropriate lane width and turning radius shall be incorporated in the site construction plans for the refuse removal vehicle to access the dumpster receptacle and to exit the property safely. (4) All businesses are required to maintain the dumpster enclosure in a continuous state of repair to include: a. The gate shall be maintained so that it is fully functional. It shall open and close as designed. b. Any walls of the enclosure that are damaged from any cause shall be repaired. (5) As of October 1, 2006, all dumpsters located in the incorporated areas of the city shall conform to all requirements for dumpster receptacle enclosures.