A. Standard Specifications. 1. All of the materials, methods of the construction, and workmanship for the work covered in reference to stormwater conveyance facility construction shall conform to the most recent Standard Specifications of the Georgia Department of Transportation (GDOT). 2. Allowable pipe material for all applications in drainage easements and public street rights-of-way, except as specified below, are aluminum-coated (Type 2) corrugated steel pipe (ASP), corrugated aluminum alloy pipe, smooth-lined corrugated high density polyethylene pipe (HDPE), or reinforced concrete pipe (RCP). Usage is summarized in the table below titled Allowable Pipe Use. 3. For roads constructed with public funds, either wholly or in part, or roads classified as major thoroughfares, materials which meet the Georgia Department of Transportation (GDOT) design standards shall be used unless an alternative is specifically approved by the city. 4. Only reinforced concrete pipe (RCP) shall be used for all dams nine (9) feet or more in height with an impounding capacity of twenty (20) acre-feet or more unless the Georgia Safe Dams Program requires another material. 5. Reinforced concrete pipe (RCP) shall be used under non-local roads when the ADT is greater than fifteen thousand (15,000) vehicles per day (vpd). Reinforced concrete pipe (RCP) or smooth-lined corrugated high density polyethylene (HDPE) pipe shall be used under nonlocal roads when the ADT is less than fifteen thousand (15,000) vpd. 6. The director may approve an alternative pipe material with the recommendation of an engineer registered in the State of Georgia. B. Minimum Pipe and Pipe Coating Requirements. The type of pipe material used shall be in accordance with subsection 16.13.A., Standard Specifications. 1. Reinforced concrete pipe shall be in no less than eight-foot joint lengths. All joints shall be bell and spigot type, with a rubber gasket conforming to ASTM C-443. Pipe shall be manufactured in accordance with AASHTO M-170 and/or ASTM C-76. Class of pipe and wall thickness shall be in accordance with 1030-D, Georgia DOT specification, Table No. 1. 2. Aluminum-coated (Type 2) steel pipe shall comply with AASHTO M-274 for the coating and AASHTO M-36 for the pipe fabrication. Aluminum alloy pipe shall comply with AASHTO M-196 for material and fabrication. 3. The director shall determine the minimum acceptable combinations of gages, diameters, and corrugation configurations for corrugated aluminum alloy pipe and pipe arches, and for corrugated aluminum-coated steel pipe and pipe arches. 4. Each end of each pipe section, to be joined by a coupling band, shall have a minimum of two (2) annular corrugations. Coupling bands shall be so constructed to lap on an equal portion of each of the pipe sections to be joined. The connecting bands shall have a minimum of two (2) annular corrugations and fully engage, over the entire pipe periphery, one (1) corrugation on each pipe. Bands shall be fabricated from the same material as the pipe. The minimum band gauges for aluminum pipe and aluminized pipe shall be as specified in AASHTO M-196, Section 19, and AASHTO M-36, Section 9, respectively. 5. Gaskets may be required as determined by the city in the field, shall be either sleeve type or O-ring type and shall meet the requirements for gaskets as specified in AASHTO M-36, Section 9.3. C. Structural Plate Drainage Structures. Structural plate drainage structures shall conform to the following specifications: 1. Corrugated aluminum alloy structural plate pipe, pipe arches and arches shall consist of aluminum plates and galvanized bolts and nuts of the size, shape and thickness as shown on the approved plans. These structures shall conform to the requirements of AASHTO M-219. D. Smooth Interior Corrugated Polyethylene Pipe. 1. This specification applies to high density polyethylene corrugated pipe with an integrally formed smooth-lined interior (HDPE). HDPE pipe manufacturers shall be approved by the director. 2. This pipe shall conform to the requirements of AASHTO M-294, Type S. 3. Joints shall be as recommended by the manufacturer and approved by the city. Connections shall create a soil tight joint at a minimum and shall use a rubber gasket, which conforms to ASTM F-477. 4. Installation shall be in accordance with ASTM Recommended Practice D2321, AASHTO Section 30, or as specified by the city. 5. Certification from the manufacturer that the product was manufactured, tested, and supplied in accordance with this specification shall be furnished to the city upon request. Allowable Pipe Use Pipe Type | Reinforced Concrete Pipe | Metal Pipe | Plastic Pipe Aluminized Type 2 Steel | Polymer Precoat Steel | Aluminum Alloy | Corrugated Polyethylene | Smoothed—Lined High Density Polyethylene Type "S" Specifications (See Note 1) | ASTM C76, AASHTO M170 | ASTM A760, A929; AASHTO M36, M274 | ASTM A742, A762; AASHTO M36, M245, M246 | ASTM B744, B745; AASHTO M196, M197, GDT17 | AASHTO M252 | ASTM F-2306; AASHTO M294 (See Note 2) Minimum thickness/class | Per GDOT Std 1030D | Per GDOT Std 1030D | Per GDOT Std 1030D | Per GDOT Std 1030D | AASHTO M252 | AASHTO M294 Type Installation Longitudinal | X | X | X | X | X Cross drains on road w/over 15,000 ADT | Cross drain <10 percent slope | X Cross drain > 10 percent slope | Check w/HCDOT concerning pipe type to be used when x-drain > 10 percent and ADT > 15,000 Cross drains on nonlocal road w/less than 15,000 ADT | Cross drain <10 percent slope | X | X Cross drain > 10 percent slope | X Cross drains on local road (s/d road) w/less than 15,000 ADT | Cross drain < 10 percent slope | X | X | X | X Cross drain > 10 percent slope | X | X | X Lateral systems | X | X | X | X | X Slope drain | X | X | X | X Perforated underdrain | X | X | X | X | X Dams H > 9 feet and V > 20 Ac-Ft | X Perennial streams | X | X Minimum allowable design velocity | 2.5 fps | 2.5 fps | 2.5 fps | 2.5 fps | — | 2.5 fps Reinforced concrete pipe | Aluminized type 2 Steel | Polymer precoat steel | Aluminum alloy | Corrugated polyethylene | Smooth lined high density polyethylene Type "S" Maximum allowable design velocity | 15 fps | 5 fps | 15 fps | 15 fps | — | 15 fps Minimum soil pH/resistivity | — | 6/1500 ohm/cm | 5/1500 ohm/cm | — | — | — Notes: 1) All pipe materials shall meet the minimum requirements of the Georgia Department of Transportation's Standard Specifications Construction of Transportation Systems, most current edition. 2) Allow smoothed-lined HDPE, Type S (AASHTO M294) pipe for storm (longitudinal and cross) and side drain applications through forty-eight (48) inch diameter so long as roadway's ADT is less than fifteen thousand (15,000) vehicles per day. E. Pipe Installation. 1. Installation Standards. Reinforced concrete pipe (RCP), corrugated aluminum alloy pipe, corrugated aluminum coated steel pipe, and smooth interior corrugated polyethylene pipe shall be installed in accordance with Section 550 of the Georgia DOT Standard Specifications, Construction of Roads and Bridges. Prior to approval of a final plat, the city may require the submittal of certification from a mandrel testing agency indicating that all installed pipe (other than RCP) does not exceed five percent (5%) deflection. Based on field inspections, video surveillance may be conducted by the city or required by the city on storm drain installations before approval of the final plat or issuance of the certificate of occupancy. If required, video surveillance should be done after completion of all activities that may damage the pipe but prior to the placement of base and the paving or landscaping over or near the pipe. If video surveillance indicates problems such as pipe deformation, cracking, or joint separation, the pipe shall be removed and replaced before approval. 2. Bedding. All pipe structures shall be placed on stable earth or fine granular foundation with the characteristics of which would be expected to provide long-term stability. In all live stream pipe installations, in areas of low bearing solid or non-uniform foundations, in area where rock is encountered at the foundation level, or in other locations where conditions warrant, a minimum of six (6) inches of crushed stone bedding is required (maximum size of stone shall be three-quarters (¾) inch). Geotextiles or geogrids may also be required by the city in problem areas. 3. Backfilling. Backfill for CSP, CAP, and HDPE pipe installations shall be constructed using graded aggregate base or crusher run six (6) inches below the bottom of pipe to twelve (12) inches above the pipe crown. Backfill for RCP pipe installations shall be constructed using graded aggregate base or crusher run six (6) inches below the pipe invert to one-quarter (¼) of the pipe diameter. Foundation backfill material shall be used for RCP above one-quarter (¼) of the pipe diameter (if graded aggregate base is not used above the one-quarter (¼) of the pipe diameter) as per Type I or Type II, as specified in Georgia DOT Standard Specifications. These materials shall be placed in players of no more than six (6) inches loose. Compaction of these materials shall be accomplished by hand tamping or machine tamping. Required compaction levels are as follows: a. Within Street Right-of-Way. Backfill within all street rights-of-way shall be compacted to ninety-five percent (95%) maximum density, tested using the AASHTO Method T-99. b. In Other Areas. Backfill in all other areas shall be compacted to ninety percent (90%) maximum density, tested using the AASHTO Method T-99. c. Construction Loads and Minimum Covers. If drainage pipe is installed prior to the completion of grading, a minimum of four (4) feet of fill should be provided where needed to adequately protect the drainage structure during the land development phase, unless the structure itself is designed to withstand the anticipated live load during construction. F. End Finish. 1. Headwalls or other end treatments are required on all culverts and at the outlet of all piped collection systems. Where ends of pipe are located within, or near, the right-of-way and are parallel, or nearly parallel, with the roadway, safety end sections shall be required when the posted speed limit is thirty-five (35) miles per hour and over. 2. Headwalls are to be precast concrete, stone masonry with reinforced concrete footings, or poured in place, reinforced concrete with reinforced concrete footings. Precast concrete headwalls for corrugated aluminum coated steel pipe or aluminum alloy pipe shall be made with aluminum coated steel or aluminum alloy pipe stubs. 3. End treatments that conform to the slope may be pre-cast concrete end sections; aluminum coated steel or aluminum alloy end sections, masonry, PE end sections, reinforced poured-in-place slope collars, or grouted rip-rap. Concrete and metal flared end sections shall conform to applicable Georgia DOT Standard Drawing 1120, 1122, or Detail D-39. G. Junction Boxes and Catch Basins. Junction boxes and catch basins shall have metal manhole frames and lids for access. H. Other Structures. Natural bottom arches and box culverts may be used in accordance with the latest standard specifications of the Georgia Department of Transportation. Bottomless culverts shall require that a scour analysis be done by a registered professional engineer in that field to Georgia Department of Transportation Specifications and Standards to ensure the soundness of the proposed structure.