(a) Interior pile temperatures of piles subject to this ordinance shall be monitored and recorded on a regular basis per the operational plan. Internal pile temperatures must be taken at 2/3 the pile height, 12 to 24 inches from the surface with a probe-type thermometer. Readings shall be made at not greater than 50-foot intervals along the length of the pile. (b) Once windrows exceed 158 F°, the operator must institute reasonable measures to prevent internal temperatures from continuing to rise. (c) Once windrows exceed 170 F°, the windrows must be reduced in size, be rotated, and be monitored daily until temperatures drop below 158 degrees F°. All green waste stockpiles shall be re-mixed as necessary to alleviate any fire due to spontaneous combustion or temperatures above 170 F°. (d) Windrows shall be visually inspected on a weekly basis. Once fires have been detected in any windrows at a site, this visual inspection shall be a minimum daily requirement. Daily inspections shall continue until the threat of fire no longer exists, and the director approves suspension. (e) All temperature and pile-handling records shall be kept on file at the site and be made available for inspection by department personnel. Data shall include date, time, temperature, specific location, and person conducting measurement.