A fire protection system consisting of approved monitor nozzle(s), water supply system, and fire hydrants capable of supplying the minimum required flow of 1500 GPM, shall be provided to within 500 feet of all portions of the site. Additional flows shall be provided as needed where conditions are reasonably likely to produce surface fires or internal fires.

Where fire hose houses/stations are provided, fire hydrants connected to yard mains should be provided in accordance with NFPA 24. All water sources identified for use in fire suppression efforts shall be metered.