(a) Minimum size of water mains and spacing of fire hydrants for future construction and development shall be determined according to the standards and specifications of the Butts County Water Authority. (b) In single-family approved subdivisions, at least an eight-inch pipe shall be installed, except within 300 feet of a cul-de-sac. Water flow in those lines shall provide a minimum flow of water at 750 gallons per minute. Fire hydrants shall be spaced not to exceed 500 feet. Three-way hydrants shall be installed in all areas of the county. (c) In multi-family approved subdivisions or multi-family apartment complexes, at least an eight-inch or larger pipe shall be installed, except within 300 feet of a cul-de-sac. Water flow in those lines shall provide a minimum flow of water at 750 gallons per minute. Fire hydrants shall be spaced not to exceed 500 feet. Additional fire hydrants may be required to permit all portions of buildings to be reached by hose lays of not more than 400 feet by road travel. Three-way hydrants shall be installed in all areas of the county. (d) In approved industrial and commercial areas, including, but not limited to, motels, hotels, nursing homes, hospitals, educational buildings, office buildings and other structures not listed elsewhere at least a 12-inch or larger pipe shall be installed to provide a minimum flow of water at 1,000 gallons per minute. A larger flow of water may be required pursuant to fire flow calculations. Fire hydrants shall be spaced not to exceed 400 feet.