Butts County · Code of Ordinances
Part II - OFFICIAL CODE / Chapter 38 - FIRE PREVENTION AND PROTECTION / Article III - FIRE PREVENTION
Sec. 38-86. Fire protection sprinkler ordinance.
About this text
- As published by Municode, current through 2026-04-13
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) Hotels, motels, dormitories, lodging houses or rooming houses, residential board and care facilities, multifamily residential dwellings, apartment buildings, educational occupancies, day care occupancies, and health care facilities, regardless of type of construction shall have complete, automatic fire sprinkler systems installed in accordance with NFPA installation standards.
(b) All community living arrangements shall have automatic fire sprinkler systems installed in accordance with NFPA installation standards.
(c) In addition, the NFPA Code, all day care occupancies must install an automatic sprinkler system per NFPA 13R.
(d) Care facilities shall be classified as residential group R3 occupancies in accordance with Section 310.4 of the International Building Code.
(e) Care facilities for persons receiving care that are within a single-family dwelling unit are permitted to comply with the International Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or Section P2904 of the International Residential Code.
(1) Personal care homes and adult or child day care facilities shall provide an approved state license prior to the issuance of a county business license.
(f) All group home care occupancies must install a sprinkler system in accordance with
NFPA 13R.
(g) Assembly, business, mercantile, and industrial occupancies are required to install an automatic sprinkler system where one of the following conditions exist:
(1) The building or space exceeds 5,000 square feet.
(2) The building or space has an occupant load of 100 or more.
(3) The building or space is located on a floor other than the level of exit discharge.
(h) All buildings 10,000 square feet or more under a common roof, and buildings over one story in height, or any building with an occupant load of 300 or more persons shall be sprinkled with an approved NFPA 13 system.
(i) Multi-family dwellings up to and including three stories in height shall be sprinkled with an approved sprinkler system modified to include full sprinkler coverage in all attics and breezeways.
(j) In addition to the NFPA Code any residential occupancies containing more than two dwelling units must install an approved automatic sprinkler system per NFPA 13, 13R, or 13D design requirements, as approved by the Butts County Fire Marshal and/or authority having jurisdiction, including townhouses and condominiums.
(k) Automatic residential sprinkler systems for townhouses shall be permitted to be designed and installed in accordance with NFPA 13D and shall be modified to include full sprinkler coverage in all attics and breezeways.
(l) All buildings 5,000 square feet or more in an area under a common roof where vehicles are pulled inside for the purpose of maintenance, repair, storage, or installation of all accessories shall be fully sprinkled with an approved sprinkler system except where vehicle bay areas in a building are less than or equal to 600 square feet, it shall be permissible to place up to six sprinkler heads off of the domestic water supply in lieu of sprinkling the entire building. In so doing, calculations must be performed by an approved sprinkler contractor certified by the State of Georgia and suck calculations must be shown on the plans submitted for approval by the Butts County Fire Marshal's Office.
(m) Each automatic sprinkler system required by this article shall be in accordance with one of the following:
• NFPA 13, Standard for the Installation of Sprinkler Systems.
• NFPA 130, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes.
• NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height.
(n) All buildings or structures installing a 13R sprinkler system must also install a sprinkler system in the attic.
(o) A "fire wall" shall not be considered to be a separate building so as to avoid the required automatic fire extinguishing system.
(p) Approved ventilation hoods and hood fire suppression equipment shall be installed in restaurants or other occupancies, including food trucks, with food preparation facilities having cooking appliances capable of producing grease laden vapors, such as ranges, deep fat fryers, grills, broilers, or other similar appliances. The standards for approval of such facilities shall be based on the fire code, including NFPA 96, Ventilation Control and Fire Suppression of Commercial Cooking Operations.
(q) Buildings shall be equipped with an approved standpipe system when required by the building or fire code. Required standpipes shall be installed in accordance with the building code, fire code, and NFPA 14, Installation of Standpipe and Hose Systems. Site plans with fire hydrant and FDC location must be submitted for review by the Butts County Fire Marshal.
(r) The fire department connection (FDC) must be placed at the main entrance (driveway) and out of the collapse zone of the building with no obstructions, and within 50 feet of a fire hydrant. The FDC should stand between 36 inches to 48 inches above grade. No person shall put any post or installation or structure or landscaping, nearer than 36 inches to any fire department connection (FDC) or hydrant.
(s) Before any fire protection system is installed, plans shall be submitted by the contractor installing the sprinkler system to the fire marshal's office, which shall review the plans for compliance with NFPA standards prior to stamping the plans as "reviewed." Plans must show:
(1) Proposed system design over building layout.
(2) Copy of Georgia state license.
(3) All sets of working plans shall be signed, and a certified seal placed thereon.
(4) Hydraulic calculations. Information sheets (cut sheets) on materials.
(t) Sprinkler system installers, inspectors, and maintenance personnel shall meet the Rules and Regulations for Enforcement of the Georgia Fire Sprinkler Act, O.C.G.A.
§ 120-3-19.
(u) The responsibility for annual testing and maintenance of any fire protection system is the responsibility of the owner of the property. Systems shall be inspected and tested in accordance with NFPA 13, 13D, or 13R, NFPA 25 and the manufacture's requirements.
(v) All automatic sprinkler equipment specified in this article shall be inspected at least once a year by a state certified sprinkler contractor and is always maintained by the owner or occupant in proper operative conditions. The occupant of the building containing such equipment shall promptly notify the fire marshal or the Butts County Fire Department in case such sprinkler protection is withdrawn, interrupted, curtailed, or altered.
(w) The fire protection sprinkler system shall be inspected by a fire protection sprinkler contractor to determine whether the system is in compliance with applicable codes and fully operational. The fire protection sprinkler contractor shall completely restore the system, confirm the system is in service, and submit a written statement to that effect to the fire marshal's office.
History
(Ord. of 5-10-2024, (Exh. A, § 26))
Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.