Cobb County · Code of Ordinances

Part I - OFFICIAL CODE OF COBB COUNTY, GEORGIA / Chapter 122 - UTILITIES / Article II - WATER AND WASTEWATER SYSTEMS / Division 6 - NONDOMESTIC USE OF PUBLIC WASTEWATER FACILITIES

Sec. 122-188. Interceptors.

About this text

  • As published by Municode, current through 2025-11-20
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) Definitions and abbreviations. The following definitions and abbreviations shall apply only to this section.

Access port. A structure that allows access to and inspection of the interior of the interceptor.

Automatic interior recovery device (AIRD). A plumbing appurtenance that is installed in the sanitary drainage system to intercept free-floating fats, oils and grease from wastewater discharge. Such a device operates on a time- or event-controlled basis and has the ability to remove free-floating fats, oils and grease automatically without intervention from the user except for maintenance.

Change in food type. Any modification in the types of food or beverages offered that introduces new preparation methods, equipment, or FOG-producing processes not previously utilized.

Commissary. Any licensed commercial kitchen where food, containers, and supplies can be prepared, stored, and/or handled.

Discharge permit. A written authorization issued by the county water system to a person, business, or facility allowing the direct or indirect discharge of wastewater into the public sewer system.

Effluent tee. A T-shaped pipe extending from a passive exterior device at such a depth to allow recovery and discharge of water located under the separated layer of fats, oils and grease.

Fats, oils and grease (FOG). Any substance, such as a vegetable or animal product, that is used in, or is a by-product of, the food preparation process, that turns or may turn viscous or solidifies or may solidify with a change in temperature or other conditions.

Fixtures. A receptacle or device that discharges liquid waste or liquid-borne solid waste, oil and grease-laden wastes to a drainage system. Fixtures shall include but are not limited to pot sinks; prerinse sinks; soup kettles or similar devices; work stations;

floor drains or sinks into which kettles are drained;

automatic hood wash units and dishwashers.

Food service establishment (FSE). Any user involved in the stationary or mobile preparation and/or service of food and/or drink for commercial purposes including commissaries and mobile units.

Food type. Foods and beverages that require similar methods of preparation and/or contain similar types of FOG producing ingredients.

Grease interceptor. Plumbing appurtenances that are installed in the sanitary drainage system to intercept free-floating fats, oils and grease from wastewater discharge. Separation is accomplished by air entrainment, buoyancy, interior baffling and/or gravity during a retention time of not less than 30 minutes.

Grease-laden waste. Effluent discharge that is produced from food processing, food preparation or other sources where grease, fats and oils enter automatic dishwater prerinse stations, sinks or other appurtenances.

Grease trap. See also grease interceptor or automatic interior recovery device.

Influent tee. A T-shaped pipe extending into a passive exterior device to a depth allowing greaseladen wastes to be discharged beneath the layer of separated grease in a controlled manner.

Interceptor. A device designed and installed to separate and retain for removal, by automatic or manual means, deleterious, hazardous or undesirable matter from normal wastes, while permitting normal sewage or wastes to discharge into the drainage system by gravity.

Manifest. A log or record of the volume, date of removal and disposal destination of pumped materials from a grease trap.

Mobile unit. Any food service establishment that can be a vehicle, trailer, or pushcart that cooks, prepares, or serves food and/or drinks.

Oil/water separator. An interceptor designed specifically to prevent petroleum oils from entering the sewage system or stormwater system.

Passive exterior device (PED). A grease interceptor that requires pumping and is housed outside a building or structure.

Passive interior device (PID). A grease interceptor that requires pumping and is housed inside a building or structure.

Remodeling. Activities that require a building permit, significant changes to plumbing and/or fixtures in the kitchen, or addition or deletion of dishwashing machine(s) or food waste disposal unit(s.)

Sand trap. An interceptor that prevents sand and/or grit from entering the sewage system.

Solids interceptor. A device installed to separate food wastes from the discharge prior to connecting to the grease interceptor.

User. Establishments such as food service establishments, car washes, buildings with dumpsters, garages and other operations that receive county wastewater system service.

(b) Permitting and notification requirements.

(1) Permitting requirements.

a. Each user required to install an interceptor for the purpose of recovering oil, grease, or sand as set forth in paragraphs

(c) or (d) of this section shall obtain a discharge permit from the county water

system.

b. When the name of the user operating an existing interceptor changes, the new

user shall apply for a discharge permit from the county water system.

c. When the ownership of a user operating an existing an interceptor changes, but

the name of the user does not change, the new owner of the user shall notify the county water system to transfer the discharge permit.

d. Discharge permit applications shall include the name, address, telephone number and email address of the applicant, and those factors indicating the potential for grease or grit laden waste to be introduced into the wastewater system. Following the review of the application and compliance with county requirements, the county water system shall provide the user with a discharge permit number, its expiration date, and the capacity and design requirements of a compliant interceptor. The county water system shall keep a continuous public log of all permitted users, including their registration

number, address and contact name of the user.

e. Users shall renew their discharge permit every three years by submitting a permit renewal application. The discharge

permits of interceptors found to be in compliance with existing federal, state, and local laws and regulations may be

renewed by the county water system.

f. The county water system may review discharge permits annually.

g. FSE users shall display the discharge permit certificate on a wall in an area

visible to managers.

(2) Notification requirements.

a. The user shall notify the county water system prior to the installation or repair of all interceptors. Should the interceptor be installed or repaired without proper notification, the user shall

perform all necessary repairs or modifications to achieve compliance in accordance with standards developed by county

water system.

b. The user shall notify the county water system prior to remodeling or making

changes to information submitted as part of the permit application including, but not limited to, changes in food type, an increase in seating, and/or modifications to business hours. Remodeling and/or changes to information without

notification to the county water system shall be a violation and may result in enforcement action and a requirement to increase the interceptor capacity.

(c) Food service establishment interceptor installation requirements.

(1) All users that are food service establishments (FSEs) shall provide grease interceptors that must be connected to all fixtures excluding restrooms, unless the county water system determines that the user is not required to provide grease interceptors. All costs related permitting and installing grease interceptors shall be borne by the user. Interceptors with improper connections or modifications, as determined by the county water system, are in violation and shall be subject to enforcement.

(2) Technology required. An approved grease interceptor shall be installed consisting of one of the following methods:

a. Passive technology that is an approved passive exterior device (PED).

b. Passive technology that is an approved passive interior device (PID).

(3) Prohibited discharge.

a. Wastewater from dishwasher machines or wastewater that otherwise exceeds 130 degrees Fahrenheit shall not be introduced into any interior grease interceptor.

b. Food-waste grinders shall not discharge into the building drainage system

through an interior grease interceptor unless preceded by a solids interceptor.

(4) Passive exterior device (PED) requirements.

a. Each PED design, including size, type and location shall be reviewed by county water system for substantial conformity

with a grease trap detail approved and amended from time to time by the county water system. Such PED may not be used unless approved by county water system. PEDs shall:

i. Be sized and engineered based upon the anticipated load and/or conditions of actual use.

ii. Shall be constructed of sound durable material, not subject to excessive corrosion or decay, and shall be water and gas tight.

iii. Be traffic-worthy with at least one manhole opening over each of the

influent and effluent tees. If the PED has more than two compartments, there must be a trafficworthy manhole opening over the additional compartment(s).

b. Sizing. All passive exterior devices shall be sized by the county water system in

accordance with standards developed by county water system. Changes to the FSE such as remodeling, changing food type, increasing seating, or increasing day and/or hours of operation, that alter the information submitted on the

discharge permit application may result in the county water system requiring the capacity of the PED to be increased.

(5) Interior device requirements. Interior devices may be allowed in lieu of PEDs in accordance with the following conditions:

a. A technically logistical reason exists as to why a passive exterior device cannot

be installed (i.e., conflicts with existing utilities, elevation disparities or location on a second floor).

b. The installation or use of all interior devices shall not be used unless approved by the county water system. The county

water system may reject a discharge permit application if a PED cannot be installed and a PID is found not to be adequate.

i. Passive interior devices (PIDs) shall be sized by the county water system in accordance with standards developed by the county water system Changes to the FSE, such as remodeling, changing food type, increasing seating, or increasing day and/or hours of operation, that alter the information submitted on the discharge permit application may result in the

county water system requiring the capacity of the PED to be increased.

ii. New automatic interior recovery devices (AIRD) shall not be permitted. The county water system may renew or transfer permits for existing AIRDs provided they are functioning properly and sized in

accordance with standards developed by the county water system.

(6) Alternative technology/methods. Engineered alternative technology or methods may be permitted, provided the technology or method meets the minimum performance standards

set forth by this section or by the county water system.

(d) Other interceptor installation requirements. All interceptor types below must have county water system approval. All costs related to the building's sewer installation, interceptor connection and registration shall be borne by the user. Interceptors with improper connections or modifications, as determined by the county water system, are in violation and shall be subject to enforcement.

(1) Sand traps.

a. All users whose wastewater stream is associated with unusually large quantities of grit, sand or gravel shall be required to install a sand trap. All users operating car/truck wash systems shall

be required to install sand traps.

b. Design criteria. All sand traps used in conjunction with facilities other than

eating establishments shall have a capacity that will provide not less than ten minutes nor more than 30 minutes retention time at the peak eight-hour flow rate. Flow-through velocities shall not

exceed one foot per second at the peak eight-hour flow rate.

c. Compliance with plumbing code. All sand traps shall be sized, located and constructed in accordance with the provisions of the duly adopted county plumbing code where such parameters have not been otherwise set forth in this

article.

(2) Dumpster interceptor/dumpster pads.

Dumpsters/dumpster pads may be allowed to connect to the wastewater system under the following conditions:

a. The dumpster/dumpster pad shall be covered and constructed in such a manner so as to prevent stormwater runoff from entering the drainage connection; and

b. The drain shall be connected to a PED maintained by the user in the method

prescribed by this section for other PEDs.

The trap shall be at least 750 gallons and shall comply with the dumpster trap detail approved and amended from time to time by the county water system.

(3) Oil/water separator.

a. All users whose wastewater stream may include oily and/or flammable liquid

wastes shall install an interceptor.

b. Design criteria. All interceptors used in conjunction with facilities other than

eating establishments shall have a capacity that will provide not less than ten minutes nor more than 30 minutes retention time at the peak eight-hour flow rate. Flow-through velocities shall not

exceed one foot per second at the peak eight-hour flow rate.

(e) Maintenance requirements.

(1) All interceptors shall be cleaned and maintained by the user at the user's expense.

All users shall maintain their interceptors in a proper and effective manner at all times.

Maintenance shall include the complete recovery of all contents, including floating materials, wastewater and bottom sludges and solids. All interceptors shall be properly and adequately maintained to achieve the intended purpose of the device.

(2) The user shall be responsible for maintaining any interceptor in such a manner that the oil and grease discharge shall not exceed a daily maximum discharge limit of 150 mg/L for

discharges of 10,000 gallons per day and greater, nor 12.5 lbs./day for discharges less than 10,000 gallons per day. If the interceptor fails to prevent discharge over the daily maximum, the user shall be required to repair, replace or upgrade their interceptor at the user's expense.

(3) All PEDs shall be completely pumped out at a minimum of once every three months unless the county water system requires more

frequent pumping or approves less frequent pumping. The frequency of pumping shall be such as to ensure that there are no overflows of fats, oils or grease into the wastewater system. Decanting or discharging of removed waste back into the trap from which the

waste was removed or to any other grease trap or sanitary sewer connection for the purpose of reducing the volume to be hauled is prohibited.

(4) All PIDs shall be completely pumped out monthly unless the county water system

requires more frequent pumping or approves less frequent pumping. The frequency of

removal shall be such as to ensure that there are no overflows of fats, oils or grease into the wastewater system.

(5) All AIRDs shall be maintained in accordance with the manufacturer's recommendations

and a copy of same shall be maintained at the site for review and inspection by the county water system.

(6) All interceptors for facilities other than food service establishments shall be pumped out at a frequency established by the county water system to ensure that there are no overflows of sand, fats, oils or grease into the wastewater system.

(7) The user is responsible for maintaining the structural integrity of the interceptor and for ensuring that a PED interceptor complies with the county water system's design criteria and a PID interceptor complies with

manufacturer specifications. The user shall make any repairs to the interceptor required by the county water system.

(f) Requirements for the proper disposal of collected materials. Any removal and hauling of the collected materials from a grease trap, grit trap, oil-water separator, grease waste drum/barrel, or sand trap, that is not an AIRD, shall be performed by waste disposal firms holding a current registration and permit number as a commercial waste hauler under EPD rules. The collected materials shall not be returned to the wastewater system.

(g) Record keeping and reporting requirements. All users with an interceptor shall keep a record of any cleaning, servicing (i.e., waste manifests), or maintenance of their interceptor (i.e., cleaning logs for AIRDs). These records are subject to review by the county water system and shall be submitted to the county water system as required.

(1) Manifest. The removal of interceptor contents (PEDs or PIDs) shall be tracked by a state approved manifest that confirms the pumping, transport, and disposal of the contents.

a. This manifest shall contain the following information:

i. Generator information, including name, address, volume pumped, date and time of the pumping and signature of the generator verifying the information.

ii. Transporter information, including company name, address, license plate number, permit number and

driver's name and signature verifying transporter information.

iii. Receiving information, including the facility's name, address, date and time of receiving, EPD number and signature verifying receipt of the waste.

b. The manifest shall be kept on-site at the facility or, in the case of dumpster traps, at the office of the property

management company for a minimum of three years.

c. Completed grease trap cleaning manifests shall be submitted to the county water system within 14 days after the trap is cleaned.

(2) AIRD Maintenance log. For all AIRDs, a continuous log indicating each cleaning and/or maintenance for the previous 12 months,

including the disposal of the recovered grease and oil, shall be maintained. This log shall be kept in a conspicuous place where it can be inspected by the health department and/or county water system upon request. All FSEs with AIRDs installed shall submit a cleaning log quarterly to the county water system.

(h) Right to enter and inspect.

(1) Inspection and entry. Any authorized representative of the county water system bearing proper credentials and identification shall be permitted to enter and inspect all properties of users, without prior notification, for compliance with code. This right of inspection shall include the right to measure, photograph, observe, monitor, sample, test, record, review and make copies of all pertinent documents in accordance with this section.

The access port of the grease trap shall be accessible and without barriers such as heavy objects or dense flora.

(2) Inspection fees. No fee will be charged for an annual inspection by the county water system of the interceptor for the discharge permit.

However, if the grease interceptor is not in compliance with this section, a re-inspection fee may be charged for each inspection

thereafter until the interceptor is in compliance and approved by the county water system.

Failure to pay the re-inspection fee shall result in the escalation of enforcement.

(i) Violations and enforcement.

(1) Violations. It shall be unlawful for any user or customer to discharge to the county wastewater system in a manner in violation of this section, or of any conditions set forth in this article. Any user who violates any provision of this section shall, in addition to the penalties specified herein, be subject to the provisions contained in sections 122-41 through 122-56 to the extent such violations, notice and penalties are not addressed in this section.

(2) Noncompliance. If it is determined that the user has failed to comply with the provisions of this section, a written notice of violation shall be given to the use or the user's

authorized agent. If the user is not a county water system customer (e.g., if the user is a tenant in a master-metered development), then the county water system customer for the property on which the user is located shall receive a copy of the notice of violation.

The notice shall set forth the violation and the measure needed to achieve compliance.

The user shall be given a reasonable timeframe to comply. Where an emergency exists, a written warning shall be given to the user, and user will have 24 hours to comply.

(3) Failure to comply. Any user who fails to comply with a written notice of violation may be fined in an amount not to exceed $1,000.00 per violation. Each day on which noncompliance shall occur or continue shall be deemed a separate and distinct violation. Such fines may be added to the next scheduled sewer charge of the user or the customer for the property on which the user is located. The county water system shall have the power and authority to enter upon the property of any user who fails to comply with a notice of violation to terminate the user's water and/or wastewater service in any manner deemed

necessary and appropriate by the county water system. If a user who fails to comply with a notice of violation is not a customer, then the county water system shall have the power and authority to terminate the water and/or wastewater service of the customer for the property on which the user is located in any manner deemed necessary and appropriate

by the county water system. Additionally, the county water system may request that the board of commissioners suspend or revoke the user's business license after a show cause hearing, pursuant to sections 122-44 and 78-45.

(4) Overflow charge. Any sewer or manhole overflow traced to an inadequately operating interceptor or lack of an interceptor shall result in a service charge to the user or the customer for the property on which the user is located. The service charge shall include the cost of cleaning up the overflow and for cleaning grease out of the immediately adjacent contaminated wastewater system. A fine in an amount not to exceed $1,000.00 may be added to the service charge for each successive overflow. These charges and fines shall not impede other enforcement actions as

delineated in sections 122-41 through 122-60.

Additionally, the user or customer for the property on which the user is located, shall be responsible for payment of any fine levied by the Georgia Environmental Protection Division against the county as a result of overflows in the county wastewater system caused by grease traced to any inadequate or absent interceptor.

(5) Alternative penalties. Any violation of this section may also be enforced by a citation or accusation returnable to the magistrate court of the county pursuant to section 1-10.

History

The history line the source prints at the end of the section.

(Ord. of 6-28-88, § 3-26-99; Ord. of 12-12-00; Amd. of 2-22-11; Amd. of 2-23-16; Amd. of 11-20-25)

Meetings that refer to this section

Found 1: meetings of this government whose minutes or machine transcripts name this section, or an ordinance in its history line, newest first. Found by rule from those records' own words. A reference is a pointer to another record, not a statement that the section applies or was changed.

Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.

Version local-code:cobb-county/code/122-188@2025-11-20-6994cc5a80

The assistant can say what this section says in this edition, quoting it and linking to it. It will not apply the law to your situation, and nothing here is legal advice.