Sec. 54-59. Hydrant obstruction and hydrant maintenance.
About this text
- As published by Municode, current through 2025-11-20
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) For private fire hydrants located at one-family and two-family dwellings, including townhouses and condominiums, Cobb County Fire and Emergency Services shall have the authority to enforce all codes with regards to fire hydrants including but not limited to: location, inspections, maintenance, flow test (every three years) and obstructions. These private hydrants shall comply with the applicable codes, standards and local ordinances currently adopted by Cobb County and shall be enforceable per the terms of section 54-51 of this chapter.
(b) All hydrants shall be painted silver as needed.
Reflective tape a minimum of one-inch wide shall be placed around the entire circumference of the bonnet with the ends overlapping a minimum of one inch.
White reflective tape shall be used on all public fire hydrants. Orange reflective tape shall be used on all fire hydrants that are not owned and/or maintained by Cobb County Water System. Painted tape or worn tape shall be replaced. Contact the Cobb County Fire Marshal's Office for information on reflective tape that has been approved for use on fire hydrants.
(c) Hydrants other than those owned and/or maintained by Cobb County Water System shall have general maintenance performed annually in accordance with the currently adopted edition of NFPA 25.
Maintenance and flow test records shall be maintained on the premises for inspection by the Cobb County Fire Marshal's Office. A weather-resistant tag shall be affixed to each hydrant indicating the date of inspection, the name of the company responsible for the inspection, and the operational status of the hydrant using the following color system: green shall indicate that no deficiencies are present and the hydrant is fully operational; yellow shall indicate that deficiencies were found, but the hydrant remains functional; and red shall indicate that the hydrant is non-operational and will not function as intended. All maintenance shall be performed by a qualified company on file with the Cobb County Fire Marshal's Office.
(d) Hydrants other than those owned and/or maintained by Cobb County Water System shall be flow tested every three years. Flow testing shall be done in accordance with requirements in the American Water Works Association M17 manual, "Installation, Field Testing, and Maintenance of Fire Hydrants." A site map showing flow and residual hydrants (numbered appropriately) shall be provided with each report. The flow test shall be performed by a qualified company on file with the Cobb County Fire Marshal's Office.
(e) All hydrants shall be installed and maintained such that the center of any hose outlet shall not be less than 18 inches above final grade.
(Ord. of 7-26-05; Ord. of 7-25-06; Amd. of 2-24-15;
Amd. of 11-20-25)
Meetings that refer to this section
- Cobb County Board of Commissioners, November 12, 2025 (Minutes)Refers to this section in the minutes: “Sec. 54- 59”
Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.