(a) Purpose. (1) To protect the public potable water supply served by the Columbia County Water and Sewer Services from the possibility of contamination or pollution by containment, within its customers internal distribution system, such contaminants or pollutants which could backflow or back-siphon into the public water system. (2) To promote the elimination or control of existing cross-connections, actual or potential, between its customers in-plant potable water system, and non-potable systems. (3) To provide for the maintenance of a continuing program of cross-connection control which will effectively prevent the contamination or pollution of all potable water systems by cross-connection. (b) Authority. (1) The Federal Safe Drinking Water Act of 1974, and the statutes of the State of Georgia Chapters 391-3-5.13 the water purveyor has the primary responsibility for preventing water from unapproved sources, or any other substances, from entering the public potable water system. (2) Columbia County Water Utility, Rules and Regulations, adopted. (c) Responsibility. The director of water and sewer services shall be responsible for the protection of the public potable water distribution system from contamination or pollution due to the backflow or backsiphonage of contaminants or pollutants through the water service connection. If, in the judgment of the director of the water and sewer services, an approved backflow device is required at the county's water service connection to any customer's promises, the director, or his delegated agent, shall give notice in writing to said customer to install an approved backflow prevention device at each service connection to his premises. The customer shall, within 90 days install such approved device, or devices, at his own expense, and failure or refusal, or inability on the part of the customer to install said device or devices within 90 days, shall constitute a ground for discontinuing water service to the premises until such device or devices have been properly installed. Backflow assemblies are to be installed by a licensed plumber, licensed fire protection system installer, and/or licensed underground utility contractor on all new installations only. Backflow assemblies that are retrofits and upgrades must be installed by a licensed plumber. All repairs are to be made by a licensed master plumber or someone certified by the State of Georgia in backflow device repair. The device requires an initial test within five days of installation and then annually tested by a certified backflow tester to assure that it is functioning correctly and forwarded to the compliance office. (d) Definitions. Approved. Accepted by the director of the water and sewer services as meeting an applicable specification stated or cited in this regulation, or as suitable for the proposed use. Auxiliary water supply. Any water supply, on or available, to the premises other than the purveyor's approved public potable water supply. Backflow. The flow of water or other liquids, mixtures or substances, under positive or reduced pressure in the distribution pipes of a potable water supply from any source other than its intended source. Backflow preventer. A device or means designed to prevent backflow or backsiphonage. Most commonly categorized as air gap, reduced pressure principle device, double check valve assembly, pressure vacuum breaker, atmospheric vacuum breaker, hose bibb vacuum breaker, residential dual check, double check with intermediate atmospheric vent, and barometric loop. (1) Air gap. A physical separation sufficient to prevent backflow between the freeflowing discharge end of the potable water system and any other system. Physically defined as a distance equal to twice the diameter of the supply side pipe diameter but never less than one inch. (2) Atmospheric vacuum breaker. A device which prevents backsiphonage by creating an atmospheric vent when there is either a negative pressure or subatmospheric pressure in a water system. (3) Double check valve assembly. An assembly of two independently operating spring loaded check valves with tightly closing shut off valves on each side of the check valves, plus properly located test cocks for the testing of each check valve. (4) Hose bibb vacuum breaker. A device which is permanently attached to a hose bibb and which acts as an atmospheric vacuum breaker. (5) Pressure vacuum breaker. A device containing one or two independently operated spring loaded check valves and an independently operated spring loaded air inlet valve located on the discharge side of the check or checks. Device includes tightly closing shut-off valves on each side of the check valves and properly located test cocks for the testing of the check valve(s). (6) Reduced pressure principle backflow preventer. An assembly consisting of two independently operating approved check valves with an automatically operating differential relief valve located between the two check valves, tightly closing shutoff valves on each side of the check valves plus properly located test cocks for the testing of the check valves and the relief valve. (7) Residential dual check. An assembly of two spring loaded, independently operating check valves without tightly closing shut-off valves and test cocks. Generally employed immediately downstream of the water meter to act as a containment device. Backpressure. A condition in which the owners system pressure is greater than the suppliers system pressure. Backsiphonage. The flow of water or other liquids, mixtures or substances into the distribution pipes of a potable water supply system from any source other than its intended source caused by the sudden reduction of pressure in the potable water supply system. Commissioners. Columbia County Board of Commissioners. Containment. A method of backflow prevention which requires a backflow prevention preventer at the water service entrance. Contaminant. A substance that will impair the quality of the water to a degree that it creates a serious health hazard to the public leading to poisoning or the spread of disease. Cross-connection. Any actual or potential connection between the public water supply and a source of contamination or pollution. Department. Columbia County Water and Sewer Services. Director of water and sewer services. The director, or his delegated representative in charge of the Columbia County Water and Sewer Services, is invested with the authority and responsibility for the implementation of a cross-connection control program and for the enforcement of the provisions of the chapter. DNR. Department of Natural Resource. EPD. Environmental Protection Division. Fixture isolation. A method of backflow prevention in which a backflow preventer is located to correct a cross-connection at an in-plant location rather than at a water service entrance. Owner. Any person, who has legal title to, or license to operate or habitat in, a property upon which a cross-connection inspection is to be made or upon which a cross-connection is present. Person. Any individual, partnership, company, public or private corporation, political subdivision or agency of the state department, agency or instrumentality or the United States or any other legal entity. Permit. A document issued by the Columbia County Water and Sewer Services Compliance Office which allows the use of a backflow preventer. Pollutant. A foreign substance, that if permitted to get into the public water system, will degrade its quality so as to constitute a moderate hazard, or impair the usefulness or quality of the water to a degree which does not create an actual hazard to the public health but which does adversely and unreasonably effect such water for domestic use. Water service entrance. That point in the owners water system beyond the sanitary control of the district; generally considered to be the outlet end of the water meter and always before any unprotected branch. (e) Administration. (1) The Columbia County Water and Sewer Services will operate a cross-connection control program, to include the keeping of necessary records, which fulfills the requirements of the commission's crossconnection regulations and is approved by the commission. (2) The owner shall allow his property to be inspected for possible cross-connections and shall follow the provisions of the department's program and the commission's regulations if a cross-connection is permitted. (3) If the Columbia County Water and Sewer Services requires that the public supply be protected by containment, the owner shall be responsible for water quality beyond the outlet end of the containment device and should utilize fixture outlet protection for that purpose. He may utilize public health officials, or personnel from the Columbia County Water and Sewer Services, or their delegated representatives, to assist him in the survey of his facilities and to assist him in the selection of proper fixture outlet devices, and the proper installation of these devices. (f) Requirements. (1) Columbia County Water Utility. a. On new installations, the Columbia County Water and Sewer Services will provide on-site evaluation and/or inspection of plans in order to determine the type of backflow preventer, if any, that will be required, will issue permit, and perform inspection and testing. In any case, a minimum of a double check valve with a wye strainer will be required in any new commercial construction and a minimum of a dual check on any residential. b. For premises existing prior to the start of this program, the Columbia County Water and Sewer Services will perform evaluations and inspections of plans and/or premises and inform the owner by letter of any corrective action deemed necessary, the method of achieving the correc- tion, and the time allowed for the correction to be made. Ordinarily, 90 days will be allowed, however, this time period may be shortened depending upon the degree of hazard involved and the history of the device(s) in question. c. The Columbia County Water and Sewer Services will not allow any cross-connection to remain unless it is protected by an approved backflow preventer for which a permit has been issued and which will be regularly tested to insure satisfactory operation. d. If the Columbia County Water and Sewer Services determines at any time that a serious threat to the public health exists, the water service will be terminated immediately. e. The Columbia County Water and Sewer Services shall have on file, a list of private contractors who are certified backflow device testers. All charges for these tests will be paid by the owner of the building or property. f. The Columbia County Water and Sewer Services requires all reduced pressure principle devices and double check valve backflow preventers include the installation of strainers located immediately upstream of the backflow device. The installation of strainers will preclude the fouling of backflow devices due to both foreseen and unforeseen circumstances occurring to the water supply system such as water main repairs, water main breaks, fires, periodic cleaning, and flushing of mains, etc. These occurrences may stir up debris within the water main that will cause fouling of backflow devices installed without the benefit of strainers. (2) Owner. a. The owner shall be responsible for the elimination or protection of all cross-connections on his premises. b. The owner, after having been informed by a letter from the department, shall at his expense, install, maintain, and test, or have tested, any and all backflow preventers on his premises. c. The owner shall correct any malfunction of the backflow preventer which is revealed by periodic testing. d. The owner shall inform the Columbia County Water and Sewer Services of any proposed or modified crossconnections and also any existing cross-connections of which the owner is aware but has not been found by the department. e. The owner shall not install a bypass around any backflow preventer unless there is a backflow preventer of the same type on the bypass. Owners who cannot shut down operation for testing of the device(s) must supply additional devices necessary to allow testing to take place. f. The owner shall install backflow preventers in a manner approved by the Columbia County Water Utility. g. The owner shall install only backflow preventers approved by the Columbia County Water and Sewer Services or the EPD. h. Any owner having a private well or other private water source, must have a permit if the well or source is cross-connected to the Columbia County Water Utility's system. Permission to cross-connect may be denied by the Columbia County Water Utility. The owner may be required to install a backflow preventer at the service entrance if a private water source is maintained, even if it is not cross-connected to the Columbia County Water Utility's system. i. In the event the owner installs plumbing to provide potable water for domestic purposes which is on the Columbia County Water Utility's side of the backflow preventer, such plumbing must have its own backflow preventer installed. j. The owner shall be responsible for the payment of all fees for permits, annual or semi-annual device testing, retesting in the case that the device fails to operate correctly, and second re-inspections for non-compliance with the Columbia County Water Utility. (g) Degree of hazard. The Columbia County Water and Sewer Services recognizes the threat to the public water system arising from crossconnections. All threats will be classified by degree of hazard and will require the installation of approved reduced pressure principle backflow prevention devices or double check valves. (h) Permits. The Columbia County Water and Sewer Services shall not permit a cross-connection within the public water supply system unless it is considered necessary and that it cannot be eliminated. (1) Cross-connection permits that are required for each backflow prevention device are obtained from the Columbia County Water Utility. (2) Permits shall be renewed annually and are non-transferable. Permits are subject to revocation and become immediately revoked if the owner should so change the type of cross-connection or degree of hazard associated with the service. (3) An initial inspection permit is required on new residential dual check backflow preventer. (i) Existing in-use backflow prevention devices. Any existing backflow preventer shall be allowed by the Columbia County Water and Sewer Services to continue in service unless the degree of hazard is such as to supersede the effectiveness of the present backflow preventer, or result in an unreasonable risk to the public health. Where the degree of hazard has increased, an in the case of a residential installation converting to a business establishment, any existing backflow preventer must be upgraded to a reduced pressure principle device, or a reduced pressure principle device must be installed in the event that no backflow device was present. (j) Periodic testing. (1) All backflow devices shall be tested and inspected at least annually. (2) Testing must be performed by licensed backflow tester approved by the State of Georgia. (3) Any backflow preventer which fails during a periodic test will be repaired or replaced at owner's expense. When repairs are necessary, upon completion of the repair the device will be retested at owner's expense to insure correct operation. High hazard situations will not be allowed to continue unprotected if the backflow preventer fails the test and cannot be repaired immediately. In other situations, a compliance date of not more than 30 days after the test date will be established. The owner is responsible for spare parts, repair tools, or a replacement device. Parallel installation of two devices is an effective means of the owner insuring that uninterrupted water service during testing or repair of devices and is strongly recommended when the owner desires such continuity. Backflow prevention devices will be tested more frequently than specified in subsection (1), above, in cases where there is a history of test failures and the Columbia County Water and Sewer Services feels that due to the degree of hazard involved, additional testing is warranted. Cost of the additional tests will be borne by the owner. (k) Records and reports. (1) Records. The Columbia County Water and Sewer Services will initiate and maintain the following: a. Master files on customer crossconnection tests and/or inspections. b. Master files on cross-connection permits. c. Copies of permits and permit applications. d. Copies of lists and summaries supplied to the EPD. (2) Reports. The Columbia County Water and Sewer Services will submit the following to the EPD. a. Initial listing of low hazard crossconnections to the state. b. Initial listing of high hazard crossconnections to the state. c. Annual update lists of subsection a. and b. above. d. Annual summary of cross-connection inspections to the state. (l) Fees and charges. (1) The Columbia County Board of Commissioners has established fees under this article or charges for the following services or permits: a. Initial inspection fees. b. Annual inspection fees. c. Water trucks and tank permit fee. d. Citations and violations. (2) A list of the fees is on file at the clerk of court and the Columbia County Water Utility. (3) The fees for such inspections shall be issued for a period of one year. All permits will expire at 12:00 midnight on the date specified on the permit as determined by the Columbia County Water Utility. (4) Citations and violations for lack of compliance will be determined and applied to the inspection fee. (m) Water trucks and tanks inspection and permit fee. (1) Water trucks and tanks shall be inspected annually by Columbia County Water and Sewer Services and be issued a permit number and decal that shall be placed on the tank. (2) Water trucks and tanks shall have a RFZ backflow assembly or an air gap two times the diameter of the fill pipe and not less than one inch. (3) The fees for such inspections shall be issued for a period of one year. All permits will expire at 12:00 midnight on the date specified on the permit as determined by the Columbia County Water Utility. (4) Citations for lack of compliance will be determined. (5) The Columbia County Board of Commissioners has established fees under this article or charges for the following services or permits: a. Potable water trucks inspection. b. Non-potable water trucks inspection. c. Mobile tanks inspection. (6) A list of the fees is on file at the clerk of commission and the business office of Columbia County Water Utility. As an condition precedent to the granting of a permit, the permitted under this section will agree to hold harmless the county and the county's employees from any liabilities arising from the permit holder's operations under this permit. The Columbia County Water and Sewer Services may adopt, by separate ordinance, charges, surcharges, and fees for application, operation, enforcement, administration, and reimbursement of costs incurred pursuant to this section, which shall be on file at the clerk of board of commissioners and the business office of the Columbia County Water Utility.