(a) Two full sets of construction plans for any new construction or renovations shall be submitted to the fire marshal's office for review. Plan submittals must include an FMO transmittal form and must be submitted to: Coweta County Fire Rescue Attention: Fire Marshal 483 Turkey Creek Road Newnan, GA 30263 (b) Plans that are rejected and require a resubmittal shall contain two full sets of plans to be resubmitted along with an FMO transmittal form. (c) Partial plans and sheets will not be accepted for initial submissions or for resubmissions. (d) A separate submittal is required for the following: (1) Building/architectural (2) Fire alarm systems (3) Sprinkler systems/fire pumps/specialized suppression systems (4) Kitchen hood and ducts (5) Kitchen hood suppression systems (e) Building/architectural plans must be reviewed and approved before fire alarm system, sprinkler system, or other system plans will be reviewed. (f) Approved plans will be stamped by the fire marshal's office. A copy of the fire marshal's stamped plans must be on the job site. Inspections by the fire marshal's office will not be conducted if the plans stamped by the fire marshal's office are not on the job site.