Sec. 34-58. Fire department connections (FDC).

About this text

  • As published by Municode, current through 2026-05-19
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) A fire hydrant shall be located within 50 feet of the fire department sprinkler connections (FDC).

(b) A post indicator valve (PIV) shall be installed on all sprinkler systems and shall be provided with a tamper switch and lock and shall be monitored by the fire alarm system.

(c) The location of fire hydrants, fire department connections (FDC), and post indicator valves (PIV) shall be approved by the fire marshal.

History

The history line the source prints at the end of the section.

(Ord. No. 045-17, 12-19-17)