Coweta County · Code of Ordinances
Part II - CODE OF ORDINANCES / Chapter 78 - UTILITIES / Article VI - BACKFLOW PREVENTION BY CONTAINMENT
Sec. 78-100. Testing, maintenance and repairs.
About this text
- As published by Municode, current through 2026-05-19
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(1) All backflow-prevention devices, both existing and new, and all parts thereof, shall be maintained in a safe condition and in good working order.
(2) The consumer shall be responsible for the cost of testing, maintenance, and repair of all backflow-prevention devices downstream of the service-connection within the premises and on his own private system.
(3) The consumer is responsible for back-siphoned material or contamination and/or pollution through backflow, and if contamination or pollution of the Coweta County Public Potable Water Supply/System occurs through an illegal cross-connection and/or an improperly installed, maintained or repaired device, or a device that has been bypassed, he is liable for all associated costs of clean-up of the public potable water supply/system.
(4) Tests, maintenance, and repairs are to be made in accordance with the following schedule or more frequently where inspections indicate a need or are specified in the manufacturer's instructions:
(a) Fixed air gap separations shall be inspected at the time of installation and at least annually thereafter.
(b) Pressure vacuum breakers shall be inspected and tested at the time of installation and at least annually thereafter.
(c) Dual check valves shall be replaced along with the meter as determined by the Coweta County Water and Sewer Department meter change out program.
(d) Double check valve backflow preventers shall be inspected and tested at time of installation and at least annually thereafter.
(e) Reduced pressure zone backflow preventers shall be inspected and tested at time of installation and at least annually thereafter.
(f) Synthetic components within a device shall be replaced every ten years, or sooner if required.
(5) Test procedures for all backflow-prevention devices shall be as outlined in the:
University of Southern California, FCCCHR; Manual of Cross-connection Control, Latest Edition.
(6) Testing and repairs should be completed by a specialist who is certified and trained to understand the design and intended operation of the device(s) being tested. A copy of a tester's certificate(s) must be on file in the water and sewer department office. All repairs or replacements on a failed device shall be completed within 30 days of failure.
(7) A test and maintenance log for each RPZ, DCV, DDC and PVB device shall be maintained by the consumer. Following each test or repair a report must be sent to the Coweta County Water and Sewer Department, and must include the following information:
(a) Date of installation and location;
(b) Manufacturer's name and serial number;
(c) Date of each test or visual inspection;
(d) Name of authorized person performing test;
(e) Test results;
(f) Description of repairs or servicing required;
(g) Date repairs completed;
(h) Manufacturer's name and serial number of test kit.
(8) All backflow-prevention devices and logs shall be subject to periodic inspection by a representative of the Coweta County Water and Sewer Department. If a device is found to be inoperative or malfunctioning, the consumer will be given a reasonable time to complete corrections required by the inspector or representative. With the exception of the cases involving actual or imminent system contamination, the time allotted for corrections will be determined by the degree of potential hazard posed to the public potable water supply system.
(9) If the corrective measures have not been taken in the allotted time, termination of water service will be recommended. If the superintendent concurs, the consumer will receive a certified letter of intent to terminate service. Termination procedures will be initiated ten days after receipt. If the consumer completes the corrections prior to the deadline, termination procedures will be halted.
History
(Ord. of 11-15-05)
Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.