Coweta County · Code of Ordinances

Part II - CODE OF ORDINANCES / Chapter 78 - UTILITIES / Article VI - BACKFLOW PREVENTION BY CONTAINMENT

Sec. 78-98. Location and installation of devices.

About this text

  • As published by Municode, current through 2026-05-19
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(1) Location of all backflow-prevention devices shall be in an area that provides a safe working environment for testing and maintenance. This area shall be readily accessible and free from extreme cold, heat, and/or electrical hazards.

(2) Installation of all backflow-prevention devices shall be in accordance with the Georgia State Plumbing Code, the following procedures, and other applicable codes and regulations.

Installations for containment shall be by a duly licensed plumbing, mechanical, and/or utility contractor; and as approved by the Coweta County Water and Sewer Department:

(a) When a dual or double check valve backflow preventer is used in the containment concept, it shall be installed at or as close to the service-connection as practical, in an approved meter box or covered vault.

(b) When a reduced pressure zone backflow preventer is installed at the serviceconnection it shall be above ground in a structure that is protected from freezing. In lieu of the above-ground installation at the service-connection, and at the owner's request, the water purveyor and the plumbing official may allow the RPZ to be installed immediately inside the building, in which case the device would remain under the jurisdiction of the Coweta County Water and Sewer Department and subject to inspections, and testing by its authorized representative.

NOTE: When a backflow preventer is installed in a service pipe inside a structure on any premises for the purpose of containing said premises, it shall be unlawful to tap into such service pipe between the BFP and the service-connection. Any branch connection(s) on an existing service pipe shall be permanently disconnected or equipped with a backflow preventer(s) commensurate with the degree(s) of hazard.

Section 1105.2(c), Georgia State Plumbing Code.

(3) Facilities that must have continuous uninterrupted water supply shall install backflowprevention devices in parallel for testing and maintenance purposes. In no case shall a bypass arrangement be installed or maintained unless also equipped with an approved backflowprevention device.

(4) Vacuum breakers and backflow preventers equipped with atmospheric vents, or with relief openings, shall be so installed and so located as to prevent any vent or any relief opening from being submerged. They shall be installed in the position as recommended by the manufacturer, and as prescribed in the following:

(a) Vacuum breaker, atmospheric type (AVB). This device shall be at least six inches above the highest outlet or the overflow level on the nonpotable system. It shall be installed downstream of the last shut-off valve.

(b) Vacuum breaker, pressure type (PVB). This device shall be installed at least 12 inches above the highest outlet or the overflow level on the nonpotable system. It may be installed upstream of the last shut-off valve.

(c) Vacuum breaker, hose type (HVB). This device shall be installed directly on the hose threads, if not an integral part of the valve. It may not be subjected to continuous pressure, static or flowing. Nor shall it be attached to a freezeless-type hydrant unless it is a model specifically designed for the service.

(d) Backflow preventer, dual check (DuC). This assembly shall not be buried in earth, but maybe installed below grade as in a meter box. A positive shut-off valve and union shall be near the inlet and outlet sides.

(e) Backflow preventer, double check valve (DCV). This device shall not be buried in earth but may be installed below ground in a pit provided ball valve test cocks fitted with brass plugs are used. Assembly bolts on bronze DCV's installed in pits shall be resistant to electrolysis. A full-port resilient-seated ball valve in sizes through two inches, in sizes above two inches, shall be near the inlet and outlet sides of the device.

The device shall be provided with three ball valve test cocks and a fourth test cock shall be provided on the upstream side of the inlet shut-off valve. When below ground, a union or flange shall be near the inlet and outlet sides. No intervening connection(s) shall be between the shut-off valves and the backflow preventer. Except when a meter or other device with bronze strainer, integral or attached, is immediately upstream of the backflow preventer, a bronze strainer shall be provided between the inlet shut-off valve and the device on sizes through two inches. When used on sizes larger than two inches, the strainer shall be of the same material as the device.

(f) Backflow preventer with intermediate atmospheric vent (IAV). This device shall not be installed below ground. Where relief valve discharge could cause water damage, it shall be piped via an air gap, or a funnel, at the vent/relief port to a floor drain or other approved location. A positive shut-off valve and union shall be near the inlet and outlet sides of the device. Strainer to be included as in paragraph (d) above.

(g) Backflow preventer, reduced pressure zone (RPZ). This device shall not be installed below ground. Where relief valve discharge could cause water damage, it shall be piped via an air gap, or a funnel, at the vent/relief port to a floor drain or other approved location. Positive shut-off valves, test cocks, and strainer are to be provided as in paragraph (e) above. No intervening branch connection(s) shall be between the shut-offs and the backflow preventer.

NOTE: When a reduced pressure zone device is installed in a line subject to periodic no-flow conditions, and supply pressure subject to fluctuations, an auxiliary directional check with soft disc, capable of functioning in any position with the BFP may be installed, it shall be provided between the inlet shut-off valve and the BFP head to lock the supply pressure in, and prevent unnecessary discharge through the vent/relief port. Make-up lines to chilled water systems and hydronic heating systems are examples of installations where a drop in supply pressure may occur during no-flow conditions. When a water pressure reducing valve is required in the same line with the RPZ device, it is usually possible to locate the reducing valve upstream of the device and take advantage of the check valve effect of the reducing valve. In such case, the auxiliary directional check would not be required.

SPECIAL CAUTION:

THERMAL EXPANSION. When water is heated and stored in a distribution system or a branch of the system that has been closed by the installation of a backflow-prevention device or any other checking device, an approved auxiliary relief valve, or expansion chamber shall be installed to limit thermal expansion of the water being heated to not more than 80 psi no-flow pressure at any fixture on the system. Section 1112.8 of the Georgia State Plumbing Code.

Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.