(a) The holder of a county permit issued pursuant to this article shall be required to perform such monitoring and recording of process and operational parameters as deemed necessary and appropriate by the board. Monitored parameters and required measuring and recording frequencies may include, but are not limited to, one or more of the following: (1) Incinerators. a. Frequency and mass of waste charging (continuous). b. Ash generation rate (weekly). c. Primary and secondary chamber temperatures (continuous). d. Flue gas opacity (continuous). e. Auxiliary fuel usage (weekly). f. Primary and secondary combustion air flow rates (weekly). g. Fan motor current (weekly). h. Wet scrubbers (weekly). 1. Scrubber liquid header pressure. 2. Scrubber liquid flow rate. 3. Scrubber liquid pH (daily). 4. Scrubber static pressure drop. 5. Demister static pressure drop. i. Dry scrubbers and spray dry absorbers: 1. Reagent flow rate (daily). 2. Slaker slurry outlet temperature (weekly). 3. Solids recycle rate (weekly). 4. Nozzle air and slurry pressures (weekly). 5. Wet and dry bulb temperatures (weekly). j. Fabric filters: 1. Bag failure records (continuous). 2. Static pressure drop (weekly). 3. Baghouse inlet and outlet temperatures (weekly). k. Flue gas concentrations: 1. Acid gases. 2. CO. 3. 02 , CO2 . 4. Opacity. (2) Autoclaves. a. A recording thermometer shall be used during each complete cycle to ensure the attainment of a temperature of 121 degrees Celsius (250 degrees Fahrenheit) for one-half hour or longer in order to achieve decontamination of the entire load. b. Monitoring of the steam sterilization process shall be required in order to confirm the attainment of decontamination. c. Monitoring may be conducted using biological indicators or other methods as approved by the board. Indicators used to ensure the attainment of the proper temperature during steam sterilization shall be placed at the point of the load where the rate of thermal penetration is at a minimum. (b) The holder of a county incinerator permit issued pursuant to this article shall be required to perform a TCLP (Toxicity Characteristic Leaching Procedure, Method 1311, EPA Publication SW.846) analysis on the ash based upon a schedule to be determined by the board or its designee, which may include the taking of daily grab samples, the analysis of composite grab samples at such frequency as determined by the board or its designee. (c) The holder of a county permit issued pursuant to this article may be required by the board or its designee to engage in performance testing of the biomedical waste incinerator, autoclave or biomedical waste disposal facility at one or more of the following times: the initial startup of a new facility, the startup of an existing facility after significant modification or operational changes, prior to the issuance of an initial county permit, and/or the renewal of an existing county permit. Such testing may include, but shall not be limited to, the following: TCLP testing of ash, combustibility testing of ash, putrescility testing of ash, stack testing for acid gases, metals, CO, VOCs, dioxins/furans, PM, etc., biologic tracer test, temperature testing, and thermal penetration testing. (d) The holder of a county permit issued pursuant to this article shall be required to provide the board or its designee, and the county health department, environmental section, copies of all semi-annual reports submitted to the environmental protection division of the state (EPD), all notices of violation from EPD and responses thereto, EPD reports of no-notice site inspections, and the county shall be promptly notified of any occurrence of a serious nature likely to cause public concern, including, but not limited to, fire, explosion, or extensive uncontrolled emissions. (e) The holder of a county permit issued pursuant to this article shall be required to provide to the board or its designee, on an annual basis, the resumes of supervisory and management personnel responsible for the supervision and management of the incinerator facility, autoclave or biomedical waste disposal facility, and all records of training and certification relating to any employee of the biomedical waste incinerator facility, autoclave or biomedical waste disposal facility. (f) The holder of a county permit issued pursuant to this article shall be required to present an ash management plan, or decontaminated waste disposal plan in the case of autoclaves, to the board or its designee at the time that the holder of a county permit first makes application for an initial permit pursuant to this article, and annually thereafter following the issuance of the county permit for the operation of the incineration facility. Such plan shall include a description of the estimated quantity of ash or decontaminating biomedical waste to be disposed of during the upcoming year, and the names, addresses and telephone numbers of all landfills where such ash or decontaminating biomedical waste will be disposed. (g) The board or its designee shall have the right to perform inspections of the biomedical waste incinerator facility or biomedical waste disposal facility during normal operating hours without prior notice to the owner/operator of such facility. The board's or its designee's right to perform inspections under this subsection shall include the authority to perform independent testing on any aspect of the performance of the biomedical waste incinerator facility or biomedical waste disposal facility for purposes of monitoring the facility's compliance with this article. The board or its designee shall have the authority to require that the holder of a county permit issued pursuant to the article be required to install auxiliary sampling reports as a condition of its permit for the purpose of supporting inspections and independent testing. (h) All costs for testing, monitoring, inspections, generation of reports or any other general or specific requirement listed or contemplated by this section shall be the responsibility of the permit holder.