Skip to content
Georgia Commons
Menu

Douglas County · Code of Ordinances

Chapter 10 - FIRE PROTECTION

Sec. 10-17.1. Aerial fire apparatus access road.

About this text

  • As published by Municode, current through 2026-03-31
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) Buildings or portions of buildings or facilities exceeding thirty (30) feet in height above the lowest level of fire department vehicle access

shall be provided with approved fire apparatus roads capable of accommodating fire department aerial apparatus. Overhead utility and power lines shall not be located within the aerial fire apparatus access roadway.

(b) Fire apparatus access roads shall have a minimum unobstructed width of twenty six (26) feet in the immediate vicinity of any building or portion of building more than thirty (30) feet in height.

(c) At least one (1) of the required access roads meeting this condition shall be located within a minimum of fifteen (15) feet and a maximum of thirty (30) feet from the building, and shall be positioned parallel to one (1) entire side of the building.

(d) Commercial and industrial buildings exceeding thirty (30) feet or three (3) stories in height shall have at least three (3) means of fire

apparatus access for each structure.

History

The history line the source prints at the end of the section.

(Ord. of 8-18-09)

Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.

Version local-code:douglas-county/code/10-17.1@2026-03-31-7e0f427575

The assistant can say what this section says in this edition, quoting it and linking to it. It will not apply the law to your situation, and nothing here is legal advice.

Douglas County Code of Ordinances, Sec. 10-17.1. Aerial fire apparatus access road | Georgia Commons