Sec. 10-17.1. Aerial fire apparatus access road.
About this text
- As published by Municode, current through 2026-03-31
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) Buildings or portions of buildings or facilities exceeding thirty (30) feet in height above the lowest level of fire department vehicle access
shall be provided with approved fire apparatus roads capable of accommodating fire department aerial apparatus. Overhead utility and power lines shall not be located within the aerial fire apparatus access roadway.
(b) Fire apparatus access roads shall have a minimum unobstructed width of twenty six (26) feet in the immediate vicinity of any building or portion of building more than thirty (30) feet in height.
(c) At least one (1) of the required access roads meeting this condition shall be located within a minimum of fifteen (15) feet and a maximum of thirty (30) feet from the building, and shall be positioned parallel to one (1) entire side of the building.
(d) Commercial and industrial buildings exceeding thirty (30) feet or three (3) stories in height shall have at least three (3) means of fire
apparatus access for each structure.
History
(Ord. of 8-18-09)