(a) In single-family residential subdivisions if an adequate water supply is within one thousand (1,000) feet of the subdivision, the subdivider shall install or have installed a system of water mains and connections to each lot, which shall be in accordance with the adopted standards of the water and sewer authority. Said water mains shall be at least eight-inch ductile iron pipe and be installed to provide a minimum water flow of seven hundred fifty (750) gallons per minute. Fire hydrants shall be located every five hundred (500) feet and/or at every intersection, whichever is closer. Three-way fire hydrants shall be used. (b) In multifamily residential subdivisions or multifamily apartment complexes, industrial or commercial areas, to include motels, hotels, nursing homes, hospitals, education buildings, all office buildings and churches, at least eight-inch ductile iron pipe water mains shall be installed to provide a minimum water flow of one thousand (1,000) gallons per minute. Larger mains and flows may be required by the fire chief or his designee. Fire hydrants shall be three-way hydrants and shall be spaced not to exceed four hundred (400) feet with additional hydrants located as necessary to permit all portions of buildings and combustible storage to be reached by hose lays of not more than four hundred (400) feet. Fire hydrant locations shall be approved by the fire chief or his designee to allow firefighting equipment to be placed within fifteen (15) feet of said hydrants. (c) In mobile home parks, fire hydrants shall be spaced not to exceed four hundred (400) feet with a minimum of an eight-inch ductile iron water main, which shall be installed to provide a water flow of at least seven hundred fifty (750) gallons per minute. (d) Prior to any preliminary subdivision plat being submitted to the planning commission, the chief of the fire department or his designee shall review and approve the spacing of the fire hydrants, main size and water flows. (e) In all of the above requirements in section 10-19, in the event any deviation(s) are to be made, such request shall be submitted and approved in writing by the fire chief and/or his/her designee.