(a) Buildings of any type construction or occupancy greater than five thousand (5,000) square feet shall be protected throughout by an approved supervised automatic sprinkler system installed in accordance with the current State of Georgia adopted edition with amendments for NFPA 13 as modified, Standards for the Installation of Sprinkler Systems. A sprinkler control valve and water flow device shall be provided for each floor. This is not to restrict the fire chief or his designee, from requiring the installation of a water-based fire protection system and/or smoke detection system if, in the opinion of the fire chief or his designee, and for the public interest, the health and welfare of the firefighters, and the protection of human life, such a system would serve to benefit all parties that may be affected by the type of construction, hazard of content, limited access to the structure, and for other purposes. (b) Buildings of two or more stories in height shall be protected throughout by an approved supervised automatic sprinkler system as specified in subsection (a) above. These types of facilities and structures shall include commercial, multifamily dwellings, motels, hotels, and townhouses. (c) All hotels, motels, dormitories, apartments, lodgings, townhouses, rooming houses, daycare facilities with more than six (6) clients as defined by NFPA 101, Life Safety Code, and all residential board and care facilities shall be protected by an approved supervised automatic sprinkler system installed in accordance with the current state adopted edition with amendments for NFPA 13 or 13R as modified, Standards for the Installation of Sprinkler Systems in Residential Occupancies up to and including three (3) stories in height. Based on the type of construction and the tenant's ability to evacuate, the fire chief or his designee shall reserve the right to designate which system is best suited in each situation. Residential sprinklers shall be provided within dwelling units, apartments, and guest rooms. (d) Existing buildings, when required to have automatic sprinkler protection by subsections (a), (b), and (c) above, shall be retrofitted for automatic sprinklers as required by the fire chief or his designee in accordance with NFPA 13 or 13R, when the cost of renovation exceeds fifty (50) percent of the latest tax approved assessed value of the building. These buildings shall be required to upgrade in the renovation to meet all current codes, standards, and ordinances as applicable to required fire protection and life safety systems. The owner is responsible for having the system inspected and tested in accordance with the current state adopted edition with amendments for NFPA 25 as modified, Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems. (e) Where required, post indicator valves (PIV) and fire department connections (FDC) shall be located at or near the main entry to the site but no closer than one and one-half (11 /2) times the height of the building or as approved by the fire chief or his designee. Appropriate signage shall be provided to designate FDC connections. (f) All water-based fire protection systems shall be provided with electronically supervised monitoring and shall be installed in accordance with the current state adopted edition with amendments for NFPA 72 as modified, National Fire Alarm Code.