Sec. 14-15. Lithium-ion battery and lithium metal battery ordinance.

About this text

  • As published by Municode, current through 2025-08-05
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

The authority having jurisdiction ("AHJ"), the fire code official, code enforcement officer, and building official shall enforce the provisions of this chapter to ensure the safety of the public, occupants of building and structures, and the building and structures within the jurisdiction.

(1) Per federal, state, and local laws, rules, and regulations, lithium-ion battery and lithium metal batteries are considered a high-hazard commodity (H) aligning with the International Fire Code appendix E 102.1.4 and chapter 50, table 5003.1.1(1), that may produce a particular dangerous volume of fire that is difficult to extinguish.

(2) Permits.

a. Permits shall be required for storage and handling of more than fifteen (15) cubic feet of lithium-ion and lithium metal batteries and shall comply with all requirements mandated by the IBC, IFC, and county ordinances.

b. Permitting and fee requirements shall follow all guidelines established by subsection 4-40(e) of this Code.

(3) Control areas shall be established and maintained for safe storage and handling of lithium-ion and lithium metal batteries. An additional plan review fees shall be calculated and applied based on each individual control area.

(4) Storage and handling of lithium-ion batteries and lithium metal batteries shall comply with this section with the following exceptions:

a. New or refurbished batteries installed in the equipment and devices they are designed to power.

b. New or refurbished batteries packed for use with the equipment and devices they are designed to power.

c. Batteries for retail sale that are in original retail packaging that are rated at three hundred (300) watt-hours or less for lithium batteries or contain twenty-five (25) grams or less of lithium metal for lithium metal batteries.

(5) Lithium-ion and lithium metal battery storage shall be limited to ground level storage only.

(6) Storage of lithium batteries is prohibited under exit stairways.

(7) Fire areas shall be separated from each other by fire barriers having not less than two-hour fire resistance rating constructed in accordance with the building code, including horizontal assemblies.

(8) Where storage areas of lithium-ion and lithium metal batteries are in a building with other uses, battery storage areas shall be separated from the remainder of the building by two-hour rated fire barriers, including horizontal assemblies. Fire barriers shall be constructed according to the IBC.

(9) The maximum number of fire areas within a building shall be four (4). The aggregate amount of lithium-ion and lithium metal batteries stored or handled in a single fire area shall not exceed nine thousand (9,000) pounds per fire area.

(10) Exceeding the allowable number of fire areas will require an increase in the hazardous occupancy classification and construction type, and must conform to all current and/or future adopted standards regulated by the authority having jurisdiction, the fire marshal, and the building official.

(11) Lithium-ion and lithium metal batteries held in storage shall not be charged at levels exceeding fifty (50) percent of their rated capacity.

(12) Lithium-ion and lithium metal batteries held in storage shall be kept at temperatures between forty (40) and eighty (80) degrees Fahrenheit (four (4) and twenty-seven (27) degrees Celsius) to help minimize the risk of thermal runaway from manufacturing defects, damage, or internal failures.

(13) Collection containers or bins used to collect, or store lithium-ion or lithium metal batteries shall be noncombustible and shall not have an individual capacity exceeding thirty (30) gallons (one hundred thirteen and six-tenths (113.6) liters), or seven and one-half (7.5) cubic feet, or shall be approved for transportation in accordance with the department of transportation (DOT).

a. A second container or group of containers shall be separated by not less than three (3) feet of open space, ten (10) feet of open space that contains combustible materials.

b. Containers shall be located not less than ten (10) feet from exits, exits access, or exit access doors. Including containers or bins used to collect or hold damaged or discarded batteries.

c. Bins used for damaged or discarded batteries shall be constructed as above and equipped with metal lids.

d. Batteries that are damaged, or which have been designated as waste should have their battery terminals covered with insulating materials.

(14) Technical opinion and report. A third party technical opinion and report shall be prepared by a qualified expert to evaluate the fire, explosion, and health risk associated with all indoor and outdoor storage and handling area(s). The report shall be submitted to the fire code official and shall require the fire code official's approval prior to issuance of a permit. In addition to the requirements of the codes, the technical opinion and report(s) shall encompass the following criteria:

a. The potential for deflagration of flammable gases released during a thermal runaway event.

b. The basis of design for an automatic sprinkler system or other approved fire suppression and detection system. Such design basis shall reference relevant full-scale fire testing or another approved method of demonstrating sufficiency of the recommended.

c. Evaluation and recommendations for fire and explosion protection.

d. Testing requirements of UL9540A, as specified in NFPA 855 and the International Fire Code (IFC) for all energy storage systems (ESS).

e. Hazardous materials management plan in accordance with section 5001.5.1 of the IFC.

f. Hazardous materials inventory statement (HMIS) in accordance with section 5001.5.2 of the IFC.

g. Fire safety plan. A fire safety plan shall be provided in accordance to section 404 of the International Fire Code.

(15) Explosion control. Where the approved technical opinion and report recommends explosion control then such measures shall be established and approved by the AHJ.

(16) Outdoor storage. Outdoor storage of lithium-ion and lithium metal batteries, including storage beneath weather protection, shall comply with the following:

a. Battery storage shall be located not less than twenty (20) feet from any building, lot line, public street, public alley, public way or means of egress.

b. Battery storage shall be located not less than five (5) feet from any building, lot line, public street public alley, public way or means of egress where the battery storage is separated by a two-hour fire resistance-rated assembly without openings or penetrations and extending five (5) feet above and to the sides of the battery storage area(s).

c. Battery storage shall be located not less than five (5) feet from any building, lot line, public street, public alley, public way or means of egress where batteries are contained in approved prefabricated portable structures providing a complete two-hour fire resistance-rated enclosure.

d. Storage areas, including storage beneath weather-protection shall not exceed nine hundred (900) square feet. The height of battery storage in such areas shall not exceed ten (10) feet.

e. Multiple battery storage areas shall be separated from each other by not less than ten (10) feet of open space.

(17) Sprinkler requirements. All fire areas used for lithium-ion and lithium metal battery storage or handling shall be equipped throughout with an approved automatic sprinkler system according to the following:

a. All sprinkler systems shall conform to NFPA standards for plastics.

b. Sprinkler protection shall be provided as detailed in NFPA 13, standard for the installation of sprinkler systems, for cartooned unexpanded plastic commodities and for exposed unexpanded plastics.

c. An approved automatic smoke detection system that activates an approved occupant notification system shall be provided throughout each fire area.

d. Each fire area shall be provided with an approved automatic detection and alarm system. The system shall use air-aspirating smoke detection, radiant energy-sensing fire detection, or both. Continuous air sampling provides the earliest possible warning of an impending fire hazard. Aspiring detectors buy critical time needed to investigate an alarm and initiate an appropriate response to prevent injury, property damage or business disruption.

e. Where storage and handling are required by other provisions of code to be provided with a higher level of sprinkler system protection, the higher level of sprinkler system protection shall be provided.

(18) Electrical energy storage systems. ESS systems shall comply with chapter 12, section 1207 of the 2021 International Fire Code.

(19) Multi-family developments.

a. Any residential structure, other than single-family dwelling units, with an attached garage, shall have a minimum two-hour fire-resistance rated UL assembly separating the garage from any other portion of the structure.

b. Any residential development, other than of single-family dwelling units, with detached garages shall maintain at least a 20-foot separation from the residential structure to any detached garage structure within the development.

History

The history line the source prints at the end of the section.

(Ord. of 2-20-24(1))