Chapter 14 / Article III - FIRE PREVENTION

Sec. 14-38. Fire hydrants.

About this text

  • As published by Municode, current through 2025-08-05
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) Fire hydrant installation. Fire hydrants installed in the county shall meet City of Calhoun utilities engineering specifications and have a minimum of one (1) five-inch Storz connection, and two (2) two-inch connections. All fire hydrants installed in the county shall be approved by the fire code official. Fire hydrants without a pumper connection shall not be permitted. All hydrant cut-off valves shall be accessible and readily identified. Hydrant cut-off valves shall be located within a three-foot radius of the fire hydrant it serves unless otherwise authorized by the fire code official or water department official.

(b) Fire hydrant specification. Current specifications for fire hydrants must be obtained from the fire code official or water department official prior to installation.

(c) All fire hydrants will be installed on water lines no less than six (6) inches in diameter.

(d) Water supply. Adequate water supply to meet a minimum needed fire flow (NFF) shall be provided for all buildings constructed within the county. To ensure an adequate water supply exists, all proposed developments shall supply to the fire department a 24-hour water study by an independent third party. The study shall be of the immediate adjacent property to the proposed development including fire hydrant flow tests. More capacity may be required under certain circumstances by the fire code official. Water mains, appliances, and fire hydrants shall be installed to provide the NFF or available water whichever is greater.

In all cases, it is the responsibility of the property owner or developer to provide everything needed in order to provide the NFF or available water for fire protection. All fire flow tests shall be witnessed by the fire code official, or representative, prior to final approval.

Dead-end water mains shall be avoided when at all possible. All water mains shall be part of a grid, or loop, system to provide for the use of more than one (1) hydrant at a time.

(1) The needed fire flow for fire protection shall be determined by an approved method by the fire department having jurisdiction. The needed fire flow will be determined before construction commences.

(2) The minimum acceptable fire flow for residential areas shall be five hundred (500) GPM flow with twenty (20) PSI residual pressure.

(e) Locations of fire hydrants.

(1) Commercial, industrial, institutional, business, and other similar type building shall have a maximum distance from the nearest hydrant to the most remote exterior point of any building of five hundred (500) feet. The distance should be measured on a roadway surface meeting the fire department access requirements outlined in the IFC, with distance being added for turns and obstacles that may increase the way hose may be laid.

(f) Residential subdivisions shall have a hydrant located at each entrance to the subdivision with all hydrants thereafter being spaced at intervals not to exceed five hundred

(500) feet.

(g) It shall be unlawful for any person to place any object or materials that might constitute an obstruction within a three-foot radius space of a cistern or fire hydrant, or do any other act which would obstruct approaches to fire hydrants or cisterns by any member of the fire department.

(h) No person shall put any post or installation or structure or landscaping, nearer than thirty-six (36) inches to any fire hydrant.

(i) No person shall allow trees, bushes, or other growth upon the person's property to interfere with the approach to any fire hydrant or to encroach the 36-inch minimum clearance.

(j) A fire hydrant may not be painted except by an authorized agent or employee of the fire department of the county.

(k) Exceptions. Exceptions to the above shall be other installations acceptable to and approved by the authority having jurisdiction.

(l) Any new construction development unable to comply with the NFF due to lack of infrastructure of the water system shall obtain an alternative method engineered and presented for approval.

History

The history line the source prints at the end of the section.

(Ord. of 2-20-24(1))