(a) Purpose. The purpose of this division is to provide for the local amendments to the technical codes. These requirements shall be followed in addition to those included in the technical codes. (b) Footings. The following are additional requirements for footings: (1) Two (2) runs of one-half (1/2) inch (#4) minimum, steel rebar. a. Rebar shall be evenly spaced horizontally and elevated off the floor of the footing a minimum of two-and-one-half (2 1/2) inches and shall meet American Concrete Institute (ACI) Standard 318. b. Rebar must run continuously through footing, including any step downs and comers. c. Where it is necessary to piece rebar, it shall overlap a minimum of twelve (12) inches. d. All rebar shall be tied together using approved tie wire. e. Rebar shall be installed in a neat and workman like manner. (2) All grade stakes must be of metal material.