(a) In single-family approved subdivisions, at least six inch pipe shall be installed, four-inch pipe to be used when it constitutes a good gridiron and then only up to 600 feet in length between interconnecting mains. Fire hydrants shall be spaced not to exceed 600 feet. Two-way hydrants may be used in single-family subdivisions. (b) In multifamily residential subdivisions or multifamily apartment complexes, at least six-inch or larger pipe shall be installed, four-inch pipe to be used when it constitutes a good gridiron and then only up to 600 feet in length between interconnecting mains. Fire hydrants shall be two-way hydrants and shall be spaced not to exceed 500 feet with additional fire hydrants located as necessary to permit all portions of buildings to be reached by hose lays of not more than 600 feet.