(a) Urinals and associated flush valves must: (1) Use no more than 0.5 gallons of water per flush; (2) Meet the performance, testing, and labeling requirements prescribed by the American Society of Mechanical Engineers Standard A112.19.2/CSA B45.1; (3) For flushing urinals, meet all WaterSense specifications for flushing urinals; and (4) Where nonwater urinals are employed, comply with American Society of Mechanical Engineers Standard A112.19.3/CSA B45.4 or American Society of Mechanical Engineers Standard A112.19.19/CSA B45.4. (b) Non-water urinals shall be subject to the following additional minimum standards: (1) Non-water urinals shall be cleaned and maintained in accordance with the manufacturer's instructions after installation. (2) Where non-water urinals are installed they shall have a water distribution line roughed-in to the urinal location at a minimum height of 56 inches (1,422 mm) to allow for the installation of an approved backflow prevention device in the event of a retrofit. Such water distribution lines shall be installed with shut-off valves located as close as possible to the distributing main to prevent the creation of dead ends. (3) Where non-water urinals are installed, a minimum of one water-supplied fixture rated at a minimum of one water supply fixture unit shall be installed upstream on the same drain line to facilitate drain line flow and rinsing.