(a) All well contractors constructing an individual or semi-public water supply system shall conform to the following table in establishing minimum acceptable distances between a well and potential pollutants located on either the same or adjoining lots: Source of Pollution Horizontal Minimum Distance Feet From Well or Spring Property lines and rights-of-way 20 feet Sewers with leaded or mechanical joints 10 feet Septic tanks 50 feet Pit privies 100 feet Sewage sand filters 100 feet Seepage pits 100 feet Septic tank nitrification fields 100 feet Building foundations 50 feet Wells shall be located uphill when possible from these sources of pollution. (b) No well shall be located within 50 feet of the foundation of any building that has been or is to be treated for termites. This is to prevent the contamination of the well by this treatment. (c) No well shall be located in an area subject to flooding from a lake, stream or river. (d) In the construction of any particular individual or semi-public water supply system, the distance may be increased, when considered necessary by the county board of health, or its representatives in order to protect the water supply system from any potential source of contamination due to unfavorable local topography, soil or geological condition encountered. (e) For any well which is to be used for human consumption and is located in an area where livestock concentration is present, a fence should be provided to prevent the entry of livestock within a distance of not less than 50 feet from the well site.