(a) It shall be the responsibility of the person securing the permit to assure the protection of all wells from surface contamination by a four- to six-inch thick well slab extending a minimum of two (2) feet in all directions from the casing and sloping away from the well. Bored or dug wells shall be cased and cement grouted to a depth of ten (10) feet. Minimum grout thickness shall be three (3) inches. The top of the well casing shall be capped with a well cover (bored and dug wells) or a sanitary well seal (drilled wells). Sanitary seals shall be provided with a screened vent. The well cover or sanitary well seal must be a minimum of twelve (12) inches above the finished level of the slab.
(b) The opening around the drop pipe shall be sealed.
(c) After the pump has been installed, the well shall be disinfected. Bacteriological analysis of the water shall indicate a bacteriologically acceptable count for the water supply to be approved.
Bacteriologically acceptable means not more than one (1) coliform bacteria per one hundred (100) milliliters per sample of water when the membrane filter technique is used.
(d) No well used as a source of drinking water shall have a diameter of less than four (4) inches.