(a) A temporary certificate of occupancy may be issued for a portion or portions of a facility. The fire marshal shall forward written comments to the county building official allowing or disallowing occupancy of a partially completed facility. (b) All facilities described in this section shall be equipped with the following minimum features in order for temporary certificate of occupancy approval from the fire marshal's office: (1) All required portions of the means of egress shall be completed (does not include floor or wall covering). (2) All exit signage shall be in place and in proper working order. (3) All illumination of means of egress and emergency lighting fixtures shall be in place and in proper working order. (4) All required exit components shall be installed and equipped with approved hardware. (5) All automatic fire sprinkler systems (if so equipped) shall be installed, tested, and in proper working order. (6) All fire alarm and detection features (if so equipped) shall be installed, tested, and in proper working order. (7) All other required fire safety features or life safety features shall be installed tested (where applicable), and in proper working order. (8) All fire or smoke rated assemblies shall be installed and properly sealed.