Part - CODE OF ORDINANCES / Chapter 50 - ROADS / Article III - GRADING AND DRAINAGE / Division 2 - FINISHED GRADING

Sec. 50-103. Minimum specifications.

About this text

  • As published by Municode, current through 2026-04-07
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Finish grading should:

(1) Provide a minimum fall of six inches away from the structure in ten feet, except as restricted by side lot lines or other major considerations, without regard to soil type or ground frost conditions. The horizontal length of such slopes may be reduced as necessary at building corners and side yards.

(2) Provide at least six inches in 25 feet (two percent gradient) in all other unpaved areas, subject to ground frost, expansive soils, or collapsible soils, or at least three inches in 25 feet (one percent gradient) in unpaved areas not subject to such conditions.

(3) If minimum slopes cannot be attained, paved gutters or other drainage structures may be installed as required by the inspection office.

(4) All unpaved areas should slope continuously at the gradients listed in subsection (2) of this section to lower elevations off site, or to a drainage structure on the lot.

(5) Drainage swales or valleys formed by intersecting slopes should have adequate depth, width and longitudinal gradient to carry away the maximum predictable volume of stormwater runoff based on a 100-year return frequency. In no instance shall swales be positioned over sewage infiltration fields.

a. Gradients of unpaved swales should not be less than required in subsection (2) of this section for other unpaved areas.

b. Surface erosion protection should be in place to prevent accumulation of water in critical drainage swales.

(6) Where catchbasins or inlets are installed, other than at required basements areaways, finish grade elevations of adjoining areas should provide for emergency surface overflow so that, in the event of failure of catchbasins or inlets, buildings and window wells (or areaways) will be protected against flooding.

(7) Areaways for basement windows, entrances, and garage entrances should be provided with effective drainage facilities. Catchment areas should be as small as possible and must be protected from overflow of stormwater from adjacent areas.

(8) Roof drainage should discharge at least five feet away from building walls when expansive, collapsible or erodible soils are present.

History

The history line the source prints at the end of the section.

(Ord. of 11-6-1990(4), § 603)