Part - CODE OF ORDINANCES / Chapter 66 - UTILITIES / Article II - WATER / Division 2 - BACKFLOW PREVENTION
Sec. 66-61. Moderate hazard facilities and methods of correction.
About this text
- As published by Municode, current through 2026-04-07
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) Moderate hazard facilities include, but are not limited to:
(1) Fire sprinkler systems without booster pump facilities or chemical additives;
(2) Connections to tanks, lines and vessels that handle nontoxic substances;
(3) Lawn sprinkler systems without chemical injection or booster pumps; or
(4) All industrial and most commercial facilities not identified as high hazard facilities.
(b) All moderate hazard facilities must have a double checkvalve assembly as a minimum containment device.
History
(Ord. of 2-1-2000, § 1.06)