(a) How measured. The minimum required airgap shall be measured vertically from the lowest end of a potable water outlet to the flood rim or line of the fixture or receptacle into which it discharges. (b) Size. The minimum required airgap shall be twice the effective opening of a potable water outlet unless the outlet is a distance less than three times the effective opening away from a wall or similar vertical surface, in which cases the minimum required airgap shall be three times the effective opening of the outlet. In no case shall the minimum required airgap be less than shown in the following table: TABLE I. MINIMUM AIRGAPS FOR GENERALLY USED PLUMBING FIXTURES Minimum Airgap Fixture When Not Affected by Near Wall(1) (inches) When Affected by Near Wall(2) (inches) Lavatories and other fixtures with effective openings not greater than 1 /2-inch diameter. 1.0 1.50 Sink, laundry trays, goose-neck bath faucets and other fixtures with effective openings not greater than 3 1.5 2.25 Over rim bath fillers and other fixtures with effective openings not greater than one-inch 2.0 3.0 Drinking water fountains-single orifice 7 /16 (0.437) inch diameter or multiple orifices having total area of 0.150 square inches (area of circle 7 1.0 1.50 Effective openings greater than one inch . . . (3) (4) Notes: (1) Side walls, ribs, or similar obstructions do not affect airgaps when spaced from inside edge of spout opening a distance greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the diameter of the effective opening of two intersecting walls. (2) Vertical walls, ribs or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening require a greater airgap when spaced closer to the nearest inside edge of spout opening than specified in Note (1) above. The effect of three or more such vertical walls or ribs has not been determined. In such cases, the airgap shall be measured from the top of the wall. (3) Two times diameter of effective opening. (4) Three times diameter of effective opening.